beautypg.com

Slant/Fin VSL-160C Part C User Manual

13 - use, 6 – outdoor reset with room compensation

background image

73

13.10.6 – Outdoor reset
with room compensation

While in the “Installers’ Menu” (section

13.17) set the

parameter to 02.

The system will function exactly as
described in the previous “Outdoor
reset adjustment” sections except
that now the boiler pump will stay on
permanently. The opening of the room
thermostat contacts will translate into
a parallel downward movement of
the curve in Figures 13-2 and 13-3.
The value by which the curve moves
downwards can be adjusted by the

parameter present in the

“Installers’ Menu”, see section 13.17.

The

parameter can range

from 1 °F (1 °C) to 36 °F, (20°C). The
suggested values for this parameter
are:
- 18 °F (10°C) for high temperature
radiator systems;
- 6 °F (3°C) for low temperature radiant
panel systems

Values of this parameter that are
too high may translate into room
temperature instability. Values that are
too low may make the action of the
room thermostat ineffective.

Climatic adjustment with room
compensation can be used in all the
systems described in Section 13.10.1.
The advantage being that the constant
running of the pump will stabilize and
standardize the room temperatures.
This is especially true when some loops
in the heating system have considerably
greater volume than others.

13 - USE

OA = Slope of the line
Ob = Minimum heating

temperature

Oc = Maximum heating

temperature

br = “Fix point” of the angle

fulcrum of the line

b = parallel shift of the lin

e

(adjusted by the heating
knob, item “7” of fi gure 13-1)

Figure 13-3 -

Graphs of th

e outdoor reset adj

ustment

(infl uence of parameter “b”)

Figure 13-2 -

Graph of th

e outdoor reset adj

ustment

(infl uence of parameters “br”, “OA”, “Ob” and “Oc”)

Outside temperature (°F)

Calculated temperature (°F

)

Outside temperature (°F)

Calculated temperature (°F

)