Table 15-4 Alert Codes

Code

Description

50

Maximum hours count was reached

51

Illegal Modbus write was attempted

52

Modbus write attempt was rejected (NOT ALLOWED)

53

Illegal Modbus read was attempted

54

Safety processor brown-out reset occurred

55

Application processor watchdog reset occurred

56

Application processor brown-out reset occurred

57

Safety processor watchdog reset occurred

58

Alarm was reset by the user at the control

59

Burner control firing rate was > absolute max rate

60

Burner control firing rate was < absolute min rate

61

Burner control firing rate was invalid, % vs. RPM

62

Burner control was firing with no fan request

63

Burner control rate (non-firing) was > absolute max rate

64

Burner control rate (non-firing) was < absolute min rate

65

Burner control rate (non-firing) was absent

66

Burner control rate (non-firing) was invalid, % vs. RPM

67

Fan off cycle rate was invalid, % vs. RPM

68

Set point was over ridden due to sensor fault

69

Modulation was over ridden due to sensor fault

70

No demand source was set due to demand priority conflicts

71

CH 4-20mA signal was invalid.

72

Flame strength rate differential was invalid

73

Flame strength step rate was invalid

74

Periodic forced recycle

75

Absolute max fan speed was out of range

76

Absolute min fan speed was out of range

77

Fan gain down was invalid

78

Fan gain up was invalid

79

Fan minimum duty cycle was invalid

80

Fan pulses per revolution was invalid

81

Fan PWM frequency was invalid

82-83

RESERVED

84

Lead Lag CH 4-20mA water temperature setting was invalid

85

No Lead Lag add stage error threshold was configured

86

No Lead Lag add stage detection time was configured

87

No Lead Lag drop stage error threshold was configured

88

No Lead Lag drop stage detection time was configured

89

Lead Lag all boiler off threshold was invalid

90

Modulation output type was invalid

91

Firing rate control parameter was invalid

92

Forced rate was out of range vs. min/max modulation

93

Forced rate was invalid, % vs. RPM

94

Slow start ramp value was invalid

95

Slow start degrees value was invalid

96

Slow start was ended due to outlet sensor fault

97

Slow start was end due to reference set point fault

98

CH max modulation rate was invalid, % vs. RPM

99

CH max modulation rate was > absolute max rate