Table 15-3 Hold and Lockout Codes

Code

Description

Note

70

Wait for leakage test completion

Hold

71

Input power frequency mismatch

Lockout

72-77

RESERVED

78

Demand lost in run

Hold

79

Outlet high limit

Hold

80

DHW high limit

Disabled

81

Delta T limit

Hold / Lockout

82

Stack limit

Lockout

83

Delta T exchanger/outlet limit

Disabled

84

Delta T inlet/exchanger limit

Disabled

85

Inlet/Outlet inversion limit (See Table 17-1)

Hold

86

Exchanger/outlet inversion limit

Disabled

87

Inlet/exchanger inversion limit

Disabled

88

Outlet T-Rise limit (See Table 17-1)

Lockout

89

Exchanger T-rise limit

Disabled

90

Heat exchanger high limit

Disabled

91

Inlet sensor fault

Hold

92

Outlet sensor fault

Hold

93

DHW sensor fault

Hold

94

Header sensor fault

Hold

95

Stack sensor fault

Hold

96

Outdoor sensor fault

Hold

97

Internal fault: A2D mismatch

Lockout

98

Internal fault: Exceeded VSNSR voltage tolerance

Lockout

99

Internal fault: Exceeded 28V voltage tolerance

Lockout

100

Pressure sensor fault

Hold

101

Exchanger sensor fault

Disabled

102-104

RESERVED

105

Flame detected out of sequence

Hold / Lockout

106

Flame lost in MFEP

Lockout

107

Flame lost early in run

Lockout

108

Flame lost in run

Lockout

109

Ignition failed

Lockout

110

Ignition failure occurred

Hold

111

Flame current lower than WEAK threshold

Hold

112

Pilot test flame timeout

Lockout

113

Flame circuit timeout

Lockout

114-115

RESERVED

116

Wait for OK to Run

Disabled

117

Flap valve condensate fault

Disabled

118

Controller interaction system fault

Hold

119

Controller interaction communications fault

Hold

120

Flap valve backflow fault

Disabled

121

Flap valve fault

Disabled

122

Light off rate proving failed

Lockout

123

Purge rate proving failed

Lockout

124

High fire switch OFF

Hold

125

High fire switch stuck ON

Hold

126

Low fire switch OFF

Hold