beautypg.com

Reznor DV Operation Manual (for units built before August 2003) User Manual

Page 6

background image

Form

O-DV/RDF/ADF, P/N 148385, Page 5

FIGURE 4 - Burner End
Plate showing Hot Surface
Ignitor

Flame Sensor
(not shown)
Location

Burner
End Plate

burner body. The gaskets are
designed to overlap approxi-
mately 1/16" for airtight seal.

5) Follow Steps in reverse

order to re-install the pilot
assembly. Close all panels
and check for proper
operation.

NOTE: Model RDF units
manufactured prior to 3/96
have a spark ignition system.
Clean ultraviolet sensor and
spark plug. Replace as
needed.

WARNING: Burner
profile plates are
factory set to match
CFM requirements. Do
not adjust profile plates
without contacting your
Sales Representative
for technical assistance.

FIGURE 5 - Direct Fired
Burner

7. Optional

Evaporative
Cooling Module
(ADF/ADFH only)

Media - Over time, excessive amounts of mineral deposits will begin to buildup
on the media. Annually, scale and dirt should be washed off the entering sur-
face of the media. Remove the pad retainers and screen. (See Steps 1-3 and 6-
8 of Media Replacement Instructions.) Clean the media using a garden hose,
mild soap, and a soft bristled brush. When the media becomes too clogged
with mineral deposits and dirt that it cannot be cleaned, the pads should be
replaced. The average pad life is approximately three cooling seasons.

Select the correct replacement part numbers and order media pads from your
Distributor. Follow the instructions below and remove and replace pads as
shown in FIGURE 6.

R

E

Instructions for Replacing

Evaporative Cooling Media

1. Remove the three sheetmetal screws that hold the top pad retainer in

place. Release the top pad retainer from the cooling module.

2. Remove the three sheetmetal screws that hold the bottom pad retainer in

place. Release bottom pad retainer from the cooling module.

3. Disengage the screen retainers from the sides of the media.
4. Disengage inlet screen from media pads and remove.
5. Slide all media pads horizontally away from the cooling module until

clear of bottom reservoir pan. Dispose of properly.

Replacement Part No. (each)

Cellulose Fiber

Glass Fiber

(inches)

Qty

6"

12"

6"

12"

300

24 x 12

2

105985

106021

106037

106029

24 x 7-7/8

1

105986

106022

106038

106030

500

24 x 12

3

105985

106021

106037

106029

24 x 9-5/8

1

105989

106025

106041

106033

700/

48 x 12

4

107190

107194

107199

107201

1200

48 x 8-5/8

1

107191

107195

107200

107202

ADF /

ADFH

Media Pad

Sizes

Ignitor

Mixing

Plates

Burner - Full length of the

burner is made up of a series

of 6" or 12" burner sections in

a linear or oval configuration.

Burner
End Plate

Pilot Tubing