beautypg.com

Reznor ADFH Operation Manual User Manual

Page 11

background image

Form O-ADF/RDF, P/N 148385R2, Page 11

If the pilot flame rod does not sense a pilot flame, the controller shuts down the pilot

valve for a 10-second interpurge and then opens it again for a second ignition trial. If

pilot flame is not proven on the second trial, the ignition controller locks out and must

be manually reset by an interruption of the main circuit (disconnect switch).

If the burner ordered is over three feet long (Model RDF with burner Option BL7, BL8,

BL9, BL10, BL11, or BL13), a second flame rod is located at the end of the burner.

After the main gas valve(s) is energized, a 15-second trial to prove the second flame is

initiated. Failure to recognize and prove flame travel to the opposite end of the burner

will result in a pre-purge and re-try for ignition.
Service: The modular ignition controller does an internal self-check each time that it is

energized and will lockout if not found to be functioning properly. If the ignition control-

ler locks out and there is no other cause, the controller module must be replaced.

3.6 Gas Train

Including

Burner, Gas

Controls,

Manifold

Arrangements,

and Gas

Pressure

Switches

Direct-Fired Burner

Function: The design of the direct-fired burner and the controlled velocity of air at the

burner ensure complete combustion through the full range of burner sizes and gas

inputs as determined by the gas control system. The velocity of air is controlled by the

profile plates and monitored by a standard low and high air pressure switch.
Service: Refer to Paragraph 2.3.6 for instructions on burner maintenance.

WARNING: Burner profile plates are factory set to match CFM

requirements. Do not adjust profile plates without contacting your

Sales Representative for technical assistance.

Makeup Air (100% Outside Air) Gas Control Systems
• Single-Stage Gas Valve for Makeup Air (Option AG1) (750MBH

maximum)

The standard 24-volt, single state gas valve has an integral automatic electric on-off

valve, a pressure regulator, a safety pilot valve, and a manual shutoff. The valve oper-

ates in response to a call for heat from a unit-mounted air controller that monitors dis-

charge air temperature. The controller has a built-in setpoint selector from 0° - 100°F.
Due to different CFM settings and outside temperatures, the average downstream

outlet temperature may not match the control setting exactly. After the installation is

complete, adjust the setpoint to achieve the desired average outlet air temperature.

See the valve manufacturer's literature provided in the owner's envelope for specifica-

tions, wiring, and operating information.

• Two-Stage Gas Valve for Makeup Air (Option AG3) (750 MBH

maximum)

The single-stage valve is replaced by a two-stage valve having low fire and high fire

operation. The two-stage valve is controlled by a unit-mounted ductstat that monitors

discharge air temperature. The ductstat has a built-in setpoint selector from 60°-110°F.

Available for use with natural gas only.
Due to different CFM settings and outside air temperatures, the average downstream

outlet temperature may not match the ductstat setting exactly. After the installation is

complete, adjust the setpoint of the ductstat to achieve the desired average outlet air

temperature. See the valve manufacturer's literature provided in the owner's envelope

for specifications, wiring, and operating information.

• Electronic Modulation Gas Control for Makeup Air (100% Outside Air),

Options AG30, AG31, AG32, AG33, AG35, AG36

Refer to the wiring diagrams in the main electrical box to determine which controls

are on the system being serviced.

NOTE: All field-supplied control wiring for Maxitrol

controls must

not be run inside conduit with line voltage wiring. To avoid any potential

electrical interference, all field-supplied wiring for Maxitrol controls should be shielded

wiring and must be grounded at the unit only.
Function: These gas control systems provide heated makeup air at a temperature

controlled by a discharge air sensor. Makeup air gas controls apply only to systems

with 100% outside air. Each system is equipped with electronic modulation controls

that modulate burner flame from 1/25th of full fire input to full fire.

FIGURE 17 - Single-

Stage Gas Valve and

Discharge Air

Controller in Makeup

Air Gas Control

System, Option AG1

FIGURE 18 - Two-

Stage Gas Valve and

Discharge Ductstat

in Makeup Air Gas

Control System,

Option AG3

This manual is related to the following products: