16

B5sM-120ja

Factory Standard: 1.5Hp Blower Performance Chart

‡ Indicates Factory Sheave Setting

External

Unit

Static

(in-Wg)

Operating

@ 230 or

460 Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2

Turn

Open

1

Turn

Open

1.5

Turns

Open ‡

2

Turns
Open

2.5

Turns
Open

3

Turns
Open

3.5

Turns
Open

4

Turns
Open

4.5

Turns
Open

5

Turns
Open

5.5

Turns
Open

6

Turns
Open

0.1

CFM

4427

4290

4152

3979

3806

3633

3459

3291

3123

RPM

764

740

715

687

658

635

611

585

558

kW

1.51

1.39

1.26

1.14

1.01

0.90

0.79

0.72

0.65

0.2

CFM

4256

4108

3959

3787

3615

3427

3238

3058

RPM

766

742

717

689

660

636

612

586

kW

1.44

1.32

1.20

1.08

0.96

0.85

0.74

0.67

0.3

CFM

4087

3932

3776

3591

3406

3200

2993

RPM

768

744

719

691

662

639

615

kW

1.38

1.26

1.15

1.02

0.90

0.79

0.68

0.4

CFM

4155

3929

3755

3580

3361

3141

RPM

803

770

746

721

693

664

kW

1.54

1.32

1.20

1.09

0.96

0.83

0.5

CFM

3969

3704

3514

3323

3058

RPM

805

772

748

723

695

kW

1.46

1.23

1.11

1.00

0.87

0.6

CFM

3925

3767

3422

3238

3053

RPM

827

806

774

750

725

kW

1.52

1.38

1.14

1.03

0.91

0.7

CFM

3700

3549

3098

RPM

831

809

776

kW

1.43

1.27

1.04

0.8

CFM

3463

3191

RPM

832

813

kW

1.33

1.16

0.9

CFM

3107

RPM

835

kW

1.21

1.0

CFM
RPM

kW

Values includes losses for: Unit Casing, 1” Permanent Filters & Dry Evaporator Coil
When utilized with H7HK Heater kits, not all operational points shown may be available for use. Refer to the H7HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.
Refer to Blower Application Table for Alternate Accessory Drive Options Available

table 8. Blower Performance for B5sM-120ja series

(three - Phase, 10 ton Models only)