13

B5sM-090Ka

Factory Standard: 2Hp Blower Performance Chart

‡ Indicates Factory Sheave Setting

External

Unit

Static

(in-Wg)

Operation

@ 230V

Adjustable Motor Sheave Setting

Fully

Closed

1/2

Turn

Open

1

Turn

Open

1.5

Turns
Open

2

Turns
Open

2.5

Turns
Open

3

Turns
Open

3.5

Turns
Open

4

Turns
Open

4.5

Turns

Open ‡

5

Turns
Open

5.5

Turns
Open

6

Turns
Open

0.1

CFM

3747

3599

3450

RPM

614

592

570

kW

1.01

0.91

0.80

0.2

CFM

3657

3491

3330

3169

RPM

637

616

595

573

kW

1.02

0.93

0.84

0.75

0.3

CFM

3740

3585

3397

3209

3030

2851

RPM

680

659

639

619

597

575

kW

1.15

1.04

0.96

0.87

0.78

0.68

0.4

CFM

3657

3478

3298

3088

2877

2675

2472

RPM

702

682

661

641

621

600

578

kW

1.17

1.07

0.97

0.87

0.78

0.69

0.61

0.5

CFM

3700

3544

3387

3186

2985

2734

2482

RPM

739

722

705

684

663

644

624

kW

1.38

1.24

1.10

0.98

0.87

0.79

0.70

0.6

CFM

3685

3441

3262

3082

2851

2619

RPM

765

741

724

707

686

665

kW

1.28

1.28

1.14

0.99

0.89

0.79

0.7

CFM

3587

3403

3161

2944

2727

2232

RPM

788

767

743

727

710

690

kW

1.35

1.15

1.18

1.04

0.90

0.77

0.8

CFM

3293

3074

2796

2323

RPM

791

770

746

730

kW

1.25

1.06

1.07

0.89

0.9

CFM

2924

2206

RPM

794

774

kW

1.11

0.86

1.0

CFM
RPM

kW

Values includes losses for: Unit Casing, 1” Permanent Filters & Dry Evaporator Coil
When utilized with H7HK Heater kits, not all operational points shown may be available for use. Refer to the H7HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.

table 5. Blower Performance for B5sM-090Ka series

(single - Phase, 7.5 ton Models only)