B5sm-120ka – Reznor B5SM Unit Installation Manual User Manual

Page 14

background image

14

B5sM-120Ka

Factory Standard: 2Hp Blower Performance Chart

‡ Indicates Factory Sheave Setting

External

Unit

Static

(in-Wg)

Operation

@ 230V

Adjustable Motor Sheave Setting

Fully

Closed

1/2

Turn

Open

1

Turn

Open

1.5

Turns
Open

2

Turns
Open

2.5

Turns
Open

3

Turns
Open

3.5

Turns

Open ‡

4

Turns
Open

4.5

Turns
Open

5

Turns
Open

5.5

Turns
Open

6

Turns
Open

0.1

CFM

4777

4668

4529

4390

4258

4125

RPM

818

796

774

751

728

705

kW

2.01

1.82

1.67

1.53

1.39

1.25

0.2

CFM

4742

4624

4505

4366

4227

4066

3904

RPM

841

820

799

777

755

732

709

kW

2.13

1.93

1.73

1.60

1.47

1.33

1.19

0.3

CFM

4753

4619

4482

4345

4197

4048

3877

3705

RPM

860

842

822

801

779

757

734

711

kW

2.20

2.05

1.85

1.66

1.53

1.41

1.27

1.14

0.4

CFM

4750

4599

4447

4318

4189

4027

3864

3685

3506

RPM

879

862

844

825

805

782

759

736

712

kW

2.25

2.11

1.96

1.77

1.58

1.48

1.37

1.22

1.08

0.5

CFM

4599

4457

4315

2668

1020

2347

3674

3472

3270

RPM

882

865

847

829

810

786

761

737

713

kW

2.16

2.03

1.89

1.70

1.51

1.40

1.28

1.14

0.99

0.6

CFM

4461

4302

4143

3991

3838

3645

3452

3223

2994

RPM

888

869

850

831

812

788

763

739

714

kW

2.08

1.95

1.82

1.63

1.44

1.31

1.19

1.06

0.93

0.7

CFM

4385

4239

4080

3920

3776

3631

3412

3111

RPM

906

892

873

853

834

814

790

765

kW

2.15

1.94

1.82

1.70

1.53

1.36

1.24

1.09

0.8

CFM

4222

4119

3911

3703

3536

3368

3081

RPM

909

895

876

856

837

818

793

kW

2.05

1.88

1.74

1.61

1.43

1.26

1.11

0.9

CFM

4167

4035

3921

3674

3426

3276

3125

RPM

928

915

899

879

859

840

821

kW

2.22

1.95

1.78

1.63

1.47

1.31

1.15

1.0

CFM

3965

3814

3619

3362

3104

RPM

933

920

904

884

864

kW

2.09

1.83

1.62

1.48

1.35

1.1

CFM

3715

3528

RPM

941

927

kW

1.93

1.69

1.2

CFM

3407

RPM

949

kW

1.77

Values includes losses for: Unit Casing, 1” Permanent Filters & Dry Evaporator Coil
When utilized with H7HK Heater kits, not all operational points shown may be available for use. Refer to the H7HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.

table 6. Blower Performance for B5sM-120Ka series

(single - Phase, 10 ton Models only)