beautypg.com

Reznor B Option - Power Venter Installation User Manual

Page 5

background image

Form I-F/B-PV, P/N 97967R2, Page 5

(See

FIGURE 4A, page 3). Mark the three new screw holes on the top

of the heater.

2) Remove the adapter assembly and drill the holes with a 1/8" bit.

3) Attach the flue adapter assembly with five sheetmetal screws.

3. Check the Airflow

Switch

Prior to installing the venter sub-assembly, check the airflow switch for proper

operation.

4. Install Venter

Sub-assembly

The venter sub-assembly is assembled and wired at the factory. It includes the

venter wheel and housing, the motor, a junction box, an airflow switch, a time

delay relay, and a capacitor (Sizes 300 and 400 only). Position the venter sub-

assembly on the flue adapter assembly. (See

FIGURE 6.) Rotate the venter to

a position that best suits your vent pipe direction. To ensure continued proper

operation of the sail switch, DO NOT position the venter with the vent opening

in a direction below horizontal.

FIGURE 5 - Airflow (Sail) Switch

The airflow switch (A) is a small spring loaded switch

normally in an off position until the actuating button

under the hinge (B) is depressed to close the circuit. It

returns to the off position when the button is released.

A flat blade (C) -- hinged (B) at the back of the button

-- crosses the button and is extended into the airstream

of the venter. The venter motor is energized through

the thermostat, and when the fan air reaches velocity, it

pushes the airflow switch blade against the button clos-

ing the circuit to the electric gas valve.
The airflow switch blade that extends through an open-

ing (D) in the connection box (where it is located), is

bent to a 90°

angle (E) and extends into the fan housing

through a 1/4" hole. The angle of the 90° bend must be adjusted by bending backward or forward so that

the switch can fully open or close.
A definite "click" is heard both when the switch opens and closes. In the open position (when the switch

button is depressed), a full 1/32" clearance should be provided after the "click" is heard. If that is not the

case, bend the blade back at the angle until proper clearance is provided.
When the blade is released, the off "click" must occur before the blade is fully returned to rest position

against the side of the hole in the fan housing.
This check should be done

prior to installing the venter to verify proper operation of the switch. After

installing the heater, the operation of the switch must be re-checked to be sure that clearances have not

been affected.

Drill hole. Insert screw.

Drill two more "evenly

spaced" holes and fasten.

Venter

Junction

Box

Venter Motor

FIGURE 6 - Attaching the Venter Sub-Assembly

Installed Flue

Adapter Assy

Instructions:
1) Holding the venter sub-assembly

in position with the desired vent

direction (never below horizontal),

drill a hole through the connect-

ing overlap in the top portion of

the venter sub-assembly and the

adapter assembly.

2) Insert a sheetmetal screw.
3) Drill two more holes approxi-

mately 120° apart and insert

sheetmetal screws.

This manual is related to the following products: