beautypg.com

Horizontal vent terminal, Horizontal vent terminal clearances – Reznor B Option - Power Venter Installation User Manual

Page 11

background image

Form I-F/B-PV, P/N 97967R2, Page 11

Instructions for attaching double-wall (Type B) vent pipe to single-wall pipe and to the vent cap
1)
Look for the "flow" arrow on the vent pipe; attach according to the arrow. Slide the pipe so that the

single-wall pipe or the vent cap is inside the double-wall pipe.
2) Drill a hole through the pipe into the single-wall pipe or the vent cap. (Hole should be slightly smaller

than the sheet metal screw being used.) Using a 3/4" long sheet metal screw, attach the pipe. Do not over-

tighten. Repeat, drilling and inserting two additional screws evenly spaced (120° a part) around the pipe.
3) Use silicone sealant to seal any gaps. If there is an annular opening, run a large bead of sealant in the

opening. The bead of sealant must be large enough to seal the opening, but it is not necessary to fill the

full volume of the annular area.

Roof -

pitched

from

0 to 45°

A clearance thimble is required

when flue pipe extends through

combustible materials.

Follow the requirements of the

thimble or vent pipe manufacturer.

Vertical flue extension must

be 6” (152mm) higher than

anticipated snow depth but

no less than 2 ft (610mm)

above the roof. Vertical pipe

extension must be insulated.

Roof Flashing

Parapet or

Adjoining Building

6 ft (1.8M)

minimum

Reznor

Option CC1

Vent Cap

DANGER: Vent terminal arrangements illustrated are applicable only to units with a power

venter. Horizontal vent termination requires a power venter. DO NOT use a horizontal vent

with a gravity-vented heater.

Single-wall vent run and single-wall terminal end

Single-wall vent run and double-wall terminal end

VERTICAL Vent Terminal

FIGURE 15 - Vent Terminal Arrangements

Roof -

pitched

from

0 to 45°

A clearance thimble is

required when flue pipe

extends through combustible

materials. Follow the require-

ments of the double-wall pipe

manufacturer.

*Follow the instruc-

tions above to join

the double-wall vent

terminal section to

the vent run and to

seal the connection.

Vertical flue extension

must be 6” (152mm)

higher than anticipated

snow depth but no less

than 2 ft (610mm)

above the roof.

Roof Flashing

6” (152mm) minimum

Parapet or

Adjoining Building

6 ft (1.8M)

minimum

Double Wall Pipe*

Reznor

Option CC1

Vent Cap

Single-wall vent run and single-wall terminal end

Single-wall vent run and double-wall terminal end

HORIZONTAL Vent Terminal

HORIZONTAL VENT TERMINAL CLEARANCES:

The location of the termination of the horizontal vent sys-

tem must be in accordance with National Fuel Gas Code

Z223.1. Required minimum clearances are listed on the

right.

Products of combustion can cause discoloration of some

building finishes and deterioration of masonry materials.

Applying a clear silicone sealant that is normally used to

protect concrete driveways can protect masonry materials.

If discoloration is an esthetic problem, relocate the vent or

install a vertical vent.

A clearance thimble is required when flue pipe extends through combustible

materials. Follow the instructions of the thimble or vent pipe manufacturer.

Pitch flue pipe down toward

outlet 1/4” per foot for

condensate drainage. (NOTE: Slope

applies to entire horizontal vent run.)

18”

(457 mm)

minimum

Wall

Roof or Building Overhang

3 ft (1M)

minimum

6 ft (1.8M) minimum

Reznor Option CC1Vent

Cap - note positions of

vent cap openings

(shaded areas)

Parapet or

Adjoining Building

A clearance thimble is required when flue pipe extends through combustible

materials. Follow the requirements of the double-wall pipe manufacturer.

Pitch flue pipe down toward

outlet 1/4” per foot for

condensate drainage. (NOTE: Slope

applies to entire horizontal vent run.)

18”

(457 mm)

minimum

Wall

Roof or Building Overhang

3 ft (1M)

minimum

6 ft (1.8M) minimum

Reznor Option CC1

Vent Cap - note positions

of vent cap openings

(shaded areas)

Parapet or

Adjoining Building

Double-Wall

Vent Pipe*

*Follow the instructions above to join the

double-wall vent terminal section to a single-

wall vent run and to seal the connection.

6” (152mm) minimum

Structure

Minimum Clearances for Vent Termination

Location (all directions unless specified)

Forced air inlet within 10 ft (3.1m) 3 ft (0.9M) above

Combustion air inlet of another

appliance

6 ft (1.8M)

Door, window, or gravity air inlet

(any building opening)

4 ft (1.2M) horizontally; 4 ft (1.2M) below;

1 ft (.3M) above

Electric meter, gas meter * and

relief equipment

4 ft (1.2M) horizontally

Gas regulator *

3 ft (0.9M)

Adjoining building or parapet

6 ft (1.8M)

Grade (ground level)

7 ft (2.1M) above

*Do not terminate the vent directly above a gas meter or service regulator.

This manual is related to the following products: