beautypg.com

Prepare and install the flue adapter assembly – Reznor B Option - Power Venter Installation User Manual

Page 3

background image

Form I-F/B-PV, P/N 97967R2, Page 3

FIGURE 3 - Suspend the Heater from

the Two New Suspension Points
Add Nut to Lock to Inner Panel.

NOTE: Do not lock to outer panel. This may

prevent the outer side panel from being

removable for future service.

FIGURE 2 - Hanger Bracket Location

Align Clearance Hole and Cage Nut

Use Sheetmetal Screw

Removed from Heater

Position bracket, push

upward, insert screw in

slotted hole and tighten.

(Models 25 - 125 use upper

slotted hole; Models 130 -

400, use lower slotted hole.)

2. Prepare and

Install the

Flue Adapter

Assembly

Heater Size Restrictor Size

P/N

25 - 50

2-3/4" x 6"

98665

75 - 100

2" x 6"

98664

125

1" x 7"

97943

130

1-1/2" x 7-3/4"

97944

165

1" x 7"

97943

200

None

250 - 300

1-1/2" x 7-3/4"

97944

400

None

(a) Select and Attach the Flue Restrictor

WARNING: For proper and safe operation, the correct restrictor

must be installed where required. Measure the restrictor before

installing to be certain of the correct size.

There are four restrictors (rectangular pieces of sheetmetal from 1" to 2-3/4"

wide and 6" to 7-3/4" long) included in your option package. The flue restrictor

which controls the volume of dilution airflow through the drafthood and vent

pipe

must be installed on units where required to maintain safe and efficient

operation.
Using the chart on the right, determine

whether or not a restrictor is required, and

if so, which one to use.

Select the appro-

priate restrictor from the option kit. On

the

inside of the adapter assembly (See

FIGURE 4A or 4B), position the restrictor

across the flue opening. Attach the restric-

tor using two sheetmetal screws.

FIGURE 4A - Installing

a Flue Adapter Assy

(Applies to all sizes except

Size 125; see

FIGURE 4B.)

NOTES:

• The flue adapter assembly

for a Size 125 is not the

same as illustrated here;

see

FIGURE 4B, page 4.

• Heaters manufactured

prior to 10/89 have a fixed

vertical vent outlet. If the

heater being serviced has

a fixed vertical vent outlet,

install the adapter assembly

with restrictor attached over

the fixed vent outlet.

Line adapter

up with these

two holes

when marking

for holes to

drill.

(See instructions

on page 4.)

Holes for attaching restrictor
(Attach the restrictor on the inside

before installing

the flue adapter assembly.)

Flue Adapter Assembly

This manual is related to the following products: