0 dimensions, 0 mechanical, 1 assembly instructions – Reznor REC (Evaporative Cooling) Unit Installation Manual User Manual
Page 3: 1 base, cooling module, and transition duct, Figure 1 - dimensions of model rec - inches (mm), Model rec with reznor model rdf* or adf/adfh
Form I-REC, P/N 160201 R3, Page 3
2.0 Dimensions
Make certain the roof is level and free of debris where cooling module will be
mounted. Do not mount directly on soft tar roofs where the legs could sink and tilt
the cooler. Provide a level, weather-resistant, solid wood or metal base under the
cooling module support legs.
Make certain that there will be adequate clearance between the bottom of the
reservoir and the roof or platform to allow for drain and overflow pipe connections.
FIGURE 1 - Dimensions of Model REC - inches (mm)
A
Sizes 40-90 - B
23-13/16 (605)
Size 180 - B
47-13/16 (1214)
Opening Size
C Long x D High
G
1-1/32
(26)
1-1/32
(26)
2(51)
6 (152)
Adjustable Legs
16 (406) maximum
9 (229) minimum
5-9/16 (141)
2(51)
(152
)
6
21-7/16
(555
)
5-1/32
(128
)
Adjustable
21-9/16 (548)
maximum
14-9/16 (370)
minimum
Water
Connection
(1/4 tubing)
Water
Connection
(Control
Side)
Electrical
Connection
Airflow
Control Pump
Access Panel
24-1/16
(611)
27/32 (21)
F
Duct Opening
F x E
9-17/32
(242)
2(51)
Drain/Overflow
Connection
Drain/Overflow Connection
Inlet View
Control
Side
View
Outlet
View
Sizes 40-90 - E
21-5/16 (541)
Size 180 - E
45-5/16 (1151)
Size
A
C
D
F
G
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
40
28-9/16
725
26-1/2
673
24
610
23-13/16
605
26-1/16
662
50
34-1/16
865
32
813
24
610
29-5/16
745
31-9/16
802
60
39-3/16 995
37-1/2
953
24
610
34-13/16
884
37-1/16
941
70
47-13/16 1214 45-3/4
1162
24
610
43-1/16 1094
45-5/16
1145
80
53-5/16 1354 51-1/4
1302
24
610
48-9/16
1233 50-13/16
1291
90
58-13/16 1494 56-3/4 1441
24
610
54-1/16
1373
56-5/16
1430
180
58-13/16 1494 56-3/4
1441
48
1219
54-1/16
1373
56-5/16
1430
Side View
Model
REC
D
minimum
Airflow
Top view of transition
ductwork MUST be
symmetrical.
Reznor Direct-Fired Makeup Air System
Model RDF, ADF, or ADFH only
Transition
Duct
Length of Transition Duct*
RDF*
D
1 & 2
38” (965mm)
3
42” (1067mm)
ADF/ADFH
D
300 & 500
24” (610mm)
700 & 1200
30” (762mm)
FIGURE 2 - Minimum Length of Field-Installed Transition Duct - inches (mm)
D
minimum
Airflow
Blower
Cabinet
Furnace
Discharge
Plenum
Side View
Model
REC
Top view of transition
ductwork MUST be
symmetrical.
Reznor Indirect-Fired
Makeup Air System
or Air Handler
(Examples: Reznor
Model Series RXE, REB,
RPVE, RPBE,RPAK,
RGB, RPB, RGBL,
RPBL, BF, RBA,
RBL, SSCBL, PGBL)
Transition
Duct
Length of Transition
Duct
REC
D
40-90
24” (610mm)
180
30” (762mm)
Model REC with
Reznor Model
RDF* or ADF/ADFH
*Model RDF with over
17,300 CFM requires
REC 360; see
Appendix, page 11.
Model REC with
Reznor Indirect-
Fired Makeup Air
Systems
NOTE: See Appendix,
page 11, for cross-
reference chart.
3.0 Mechanical
3.1 Assembly Instructions
Be sure all preparations have been made. Review Preparation Check List in Para-
graph 1.3. Verify that all factory and field-supplied parts are available.
3.1.1 Base, Cooling Module, and Transition Duct
Assemble Legs - Using four bolts and nuts per leg, fasten two “halves” together. Leg
will have a top and bottom flange. Repeat for all four legs. (See
FIGURE 3A.) Adjust
legs to appropriate height and tighten bolts securely.
NOTE: If installing a Size
360 which is two Size 180
modules, refer to
FIGURE
17, Appendix, page 11, and
repeat assembly instruc-
tions for both modules.
REC Size
360 is two
separate Size
180 modules -
one with right
side controls
and one
with left side
controls.