Form I-REC, P/N 160201 R3, Page 11

PROBLEM

PROBABLE CAUSE

REMEDY

Pump doesn’t run – Unit

is calling for cooling (i.e.

console control switch is in

cool or summer position)

and reservoir is full .

1. Electrical connections (low voltage)

1. Verify all electrical connections. Verify correct voltage at pump terminals H

& J in REC junction box. See wiring diagram and Paragraph 4.0.

2. Electric float switch.

2. Check position of the actuators on the electric float switch.

3. Dirty pump.

3. Clean pump. See Paragraph 6.0.

4. Defective pump.

4. Replace pump.

Required water level (3”)

not being maintained

(pump & float control

system)

1. Float valve

1. Adjust float valve. See Paragraph 3.2.3.

2. Optional drain and fill valves

2. Check valves for proper operation. See

FIGURE 9.

3. Incorrect overflow pipe nipple (should

be 3-1/2”).

3. Replace pipe nipple.

4. Drain leaking.

4. Tighten drain fittings

Water running off of media

pads

1. Excessive water flow

1. Adjust ball valve in distribution line. See Paragraph 5.0.

2. Media pads need cleaned or replaced 2. Clean or replace media pads. See Paragraph 6.1.

Water not distributing

evenly

1. Distribution line clogged.

1. Flush distribution line. See Paragraph 6.2.

2. Holes in distribution line turned

2. Check position of distribution line. Holes should be spraying upward

toward diffuser. If not positioned with holes toward top, adjust position of line.

3. Pump not running on correct voltage. 3. Check voltage at pump terminal in cooling module junction box

Media pads becoming

clogged and discolored

quickly (scale and salt

deposits)

1. Bleedoff line clogged or inadequate

bleedoff (pump & float control system)

1. Clean bleed line. See Paragraph 3.2.3. A uniform buildup of minerals on

the entering air face of the media indicates insufficient bleedoff. Increase the

rate until the mineral deposits dissipate.

2. Excessive water flow.

2. Reduce flow by adjusting ball valve in distribution line. See Paragraph 5.0.

Water blowoff from media

pads or water being pulled

from reservoir.

1. Media pads installed incorrectly.

1. Install media pads correctly. See Paragraph 6.1.

2. Requires moisture elimination pad

(over 600 FPM).

2. Install moisture elimination pad. Follow instructions, Paragraph 3.1.2.

3. Water level not 3” (pump & float

system).

3. See second problem listed (Required water level not being maintained)

6.4 Troubleshooting

Chart

WARNING: Disconnect the power before servicing the cooling

module. Failure to do so can cause electrical shock, personal

injury, or death.

APPENDIX

FIGURE 17 - Model REC

Size 360 (two Size 180

evaporative cooling

modules) attached to a

Model RDF Direct-Fired

System

REC180

with right

side

controls

REC180

with left

side

controls

12” (305mm)

129-1/2’

(3289mm)

127-1/2”

(3239mm)

48”

(1219mm)

Field-Supplied

Transition Duct

1” (25mm)

1” (25mm)

56-3/4” (1441mm)

56-13/16”

(1443mm) - typ.

5-1/2”

(140mm)

Adjustable Legs

16” (406mm) max.

9” (229mm) min.

Control/Pump

Access Door

Water

Connection

1/4” tubing

2”(50mm) typ.

2”(50mm) typ.

2”(50mm)

6” (152mm)-typ.

6”

(152mm)

56-5/16”

(1430mm) - typ.

9-17/32” (242mm) - typ.

Drain & Overflow Connections

5” (127mm)

Drain & Overflow Connections

Supply

Wiring

Gas Supply

24V

Wiring

TOP

View

TOP

View

Model RDF Top View

REC Air Inlet View

7/8”

(22mm)

24-1/8” (613mm)

48” (1219mm)

Maximum

Length

Side View - Model RDF

with Model REC360 attached

Field -

Supplied

Transition

Duct

45-5/16” (1151mm)

REC

Adjustable

21-9/16” (548mm) max.

14-9/16” (370mm) min.

21-1/2” (546mm)

Dimensions -

Model REC 360

Cross-Reference

Application Chart

Reznor

®

Model Packaged Makeup Air System or Blower Cabinet

REC

RGB/RPB 75, 100, 125; RDF-1-20

40

RGB/RPB 150, 175; RDF-1-40; ADF/ADFH 300; RBA Blower Cabinet

50

RGB/RPB 200, 225

60

RGB/RPB 250, 300; RDF-1-50, -1-65; ADF/ADFH 500

70

RGB/RPB 350

80

RGB/RPB 400

90

RBL Blower Cabinet; All Sizes of RGBL/RPBL/SSCBL/PGBL; All Sizes

of RDF-2; ADF/ADFH 1200; RDF-3 up to 17,730 CFM

180

RDF Models 11,000 to 28,000 CFM

360