Reznor ADFH Unit Installation Manual User Manual

Page 23

background image

Form I-ADF, P/N 131805 R5, Page 23

Check disconnect switch to be sure that it is tightly secured against the cabinet.

If disconnect is fusible, check that fuses are installed. If fuses are not installed,

insert correct fuses. Verify continuity of fuses.

6. Open the hinged gas/electrical control compartment door --

Close all manual gas valves.

Open hinged electrical panel cover.

Check all wiring and wiring connections on gas controls and electrical components.

If equipped with any manually reset devices such as a firestat limit switch, or high

gas pressure switch, reset devices.

Optional

Freezestat

Time Delay

Relay

Optional

Firestat

Energy

Cutoff

Electrical

Box Divider

Single Speed

or Two Speed

Starter

Contactor

Optional Two

Speed Starter

Relay

Standard

Starter

Relay

24V Transformer

and/or 120V

Terminal Block with

Mounting Rail

Relays

Circuit

Analyzer Board

Inside View of

Left Side

Maxitrol

Amplifier

Ignition

Control

Board

High Air

Pressure

Switch

Low Air

Pressure Switch

Time Delay Relay

Inside View

of Top Side

Optional High AmbientLimit Control

Inside View of

Bottom Side

Terminals

Relays

FIGURE 24 - Control Locations

7. Open the hinged blower compartment door --

Remove any blocking and shipping supports.

Check all fasteners for tightness and all parts to be sure they are secure.

Rotate the blower wheel to be sure that no parts are rubbing. Check for and

remove any obstructions and/or foreign material that may damage the blower

wheel.

Check that the blower belts have correct tension (See Paragraph 6.4) and that

pulleys are in alignment and locked to the shaft.

Remove the cover from the limit switch junction box; reset manual limit switch.

Check wiring connections to limit switch, discharge air sensor, and motor.

Close blower compartment door panel; secure latches.

8. Turn ON gas supply valve and manual shutoff valve on the manifold --

Leak test gas connections upstream of the electric gas valve. Be sure all

connections are tight and leak tested.

WARNING: DO NOT TEST WITH OPEN

FLAME.

Turn OFF manual gas valves.