Troubleshooting, Error messages – PRG AutoPar User Manual 2.1 User Manual
Page 36

28
AUTOPAR
®
WASH LUMINAIRE USER MANUAL
TROUBLESHOOTING
Error Messages
After calibration, the Menu Display will cycle through any applicable error message(s), one a time until the end of the
list is reached. To review the error messages again, it will be necessary to access them using the Status function.
The following table provides all possible error messages. These errors can be reported for each mechanism (Pan, Tilt,
or Beam), except Enc Fail which does not apply to the Beam mechanism.
To access error messages:
Step
1. Press [Enter] to access top level functions.
Step
2. Press [Up] / [Down] arrows to scroll to
Fixture
menu. Press [Enter].
Step
3. Press [Up] / [Down] arrows to access
Status
. (Display will scroll through any error messages or display
OK
if no errors.)
CAUTION:
If luminaire is operated without yoke leg covers in place, pan problems will occur.
Display
Cause
No Sensor
The active sensor state was not detected during calibration. Mechanism
not moving (off sensor), sensor broken or disconnected.
Sensor On
The sensor was stuck active during calibration. Mechanism not moving
(on sensor), sensor broken or disconnected.
Enc Fail
The encoder was not changing during pan or tilt calibration. Mechanism
not moving, encoder broken or disconnected.