Specifications, S8 specifications, S8ext specifications – LAARS S8Ext - Installation Manual User Manual
Page 34

Page 34
LAARS Heating Systems
SPECIFICATIONS:
Voltage Input:
. . . . . . . . .
120 VAC 60 Hz
Power Consumption:
. . . . . . .
12 VA Max
Operating Temperature:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
°
F/-7
°
C to 120
°
F/49
°
C
Operating Humidity:
. . . . . . .
20% to 80%
Dimensions:
. . . . . . . . .
11"W x 9" H x 3 ¾
Weight:
. . . . . . . . . . . . . . .
2.5 pounds
S8 Specifications:
Lead Stage Rotation:
. . . . . . . . . . . . . . . . . . . . . . . Time ( 1 to 999 Hours (41 days)), Manual, First-On/First-Off
S8 Outputs and LEDs:
. . . . . . . . . . . . . . . . 11 N.O. S.P.S.T (8 Stages, 1 System, 1 DHW Pump, 1 Combustion Air)
S8 Inputs:
. . . . . . . . . . . . . . . . . . 1 Sys(Temp), 1 Outdoor, Return Temp, DHW Temp, Ext Setback/Shutdown, Prove
Stage Modes:
. . . . . .
Auto, Standby, Off, On
Standby Time (PID only):
.
1 to 60 minutes
Output Relay Ratings:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Amp inductive at 120 VAC 60 Hz
Add-On S8EXT Panels:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . up two S8EXT Panels using RS485
Temperature Display:
Fahrenheit or Celsius.
Display:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Graphical Alphanumeric (7 rows x 21 char. each)
Temperature Sensor Ranges:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -35
°
F/-37
°
C to 250
°
F/121
°
C
Outdoor Cutoff Range: . . . . . . . . . . . . . . . . . . . . . . . . . . .
20°F/-7°C to 100°F/38°C, ON and OFF
Set Point: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-10°F/-23°C to 230°F/110°C
External Set Point: . . . . . . . . . . . . . . . . . . . .
-10°F/-23°C to 240°F/116°C using XSIG Interface (optional)
Reset Ratio Range (Outdoor Reset Only): . . . . . . (
8:1) to (1:4) (Outdoor : System Water), and Custom Reset Ratio
Offset Adjustment (Outdoor Reset Only):
. . . . . . . . . . . . . . . . . . . . . . . . -40°F/-22°C to plus 40°F/22°C
Minimum Target (Outdoor Reset Only): . . . . . . . . . . . . . . . . . . . . . . . .
70
°
F/21
°
C to 170
°
F/77
°
C
Maximum Target (Outdoor Reset Only): . . . . . . . . . . . . . . . . . . . . . . .
90
°
F/32
°
C to 240
°
F/116°C
Reaction Time (PID only): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 to 10 minutes
Minimum Run-Time (PID only): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 to 60 minutes
Purge Delay (PID only):
.
0.0 to 10.0 minutes
Last Stage Hold (PID only):
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0°F/0°C to 30°F/17°C
Throttle Range (OSS only): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2°F/1°C to 20°F/11°C
Domestic Hot Water Priority Options:
. . . . . .Parallel Piping with Priority or without Priority and Primary Secondary
Pump Run-On:
. . . . . . . . .
0 to 60 minutes
Pump Exercise:
. . . . . . . . . . .
Yes or No
Schedules:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Day and 1 Night (Setback) settings per day
Night Setback:
. . . . .
0°F/0°C to 80°F/44°C
Power Backup:
. . . . . . . .Lithium coin battery, 100 days minimum 5 year replacement (Maintains Clock in power outages).
External Inputs:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shutdown Input, and Prove Input. (Dry Contacts Only)
Season:
. . . . . . . . . . .
Winter and Summer.
S8EXT Specifications:
Extension Numbering:
.
Toggle Switch A or B
LED:
. . . 1 Power (Dual Color Green (A)/Red (B)), 1 Communication, 8 Stage Output relays (Dual Color Green (A)/Red (B))
Stage Outputs:
. . . . . . . . .
8 N.O. S.P.S.T.
Output Relay Ratings:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Amp inductive at 120 VAC 60 Hz
Connection to S8 and another S8EXT:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Two RS485