Menu sequence, Caution – LAARS S8Ext - Installation Manual User Manual
Page 12

Page 12
LAARS Heating Systems
------ SETTINGS ------
Season
Winter
135 F
Set Point
140 F
EMS Set Point
135 F
Min Return
110 F
BACK SELECT
MENU SEQUENCE
SYS=
168
F OD=
45
F
TGT=172 F
ABC
---- LO
BOILER MENU
---- CONTROL MODE ---
Outdoor Reset
Set Point
EMS 4-20mA
BACK SAVE
---- DISPLAY UNIT ---
F
C
BACK SAVE
EMS 4mA SET POINT
100 F
[
]
BACK SAVE
---- APPLICATION ---
Heat-BreakOnRise
Cool-MakeOnRise
BACK SAVE
EMS 20mA SET POINT
170 F
[
]
BACK SAVE
---- DHW PIPING ---
Parallel
Primary/Secondary
BACK SAVE
--DHW PUMP OUTPUT--
No
Yes
BACK SAVE
--COMB. AIR OUTPUT--
No
Yes
BACK SAVE
--- SETBACK MODE --
Day/Night Schedule
External Signal
BACK SAVE
--- BURNER TYPE ----
On/Off
2-Stage
3-Stage
4-Stage
BACK SAVE
-- BOILER OUTPUT --
None
Pump
Valve
BACK SAVE
-- TOTAL BOILERS --
8
[
]
BACK SAVE
------ STAGING ------
Multiple Outputs
Single Output
BACK SAVE
------ SEQUENCE -------
Lo/Hi/Lo/Hi
Lo/Lo/Hi/Hi
BACK SAVE
--- CONTROL LOGIC---
PID
OSS
BACK SAVE
--- SENSOR FAULT ---
Stages On
Stages Off
BACK SAVE
ARE YOU SURE?
No
Yes
BACK SAVE
EMS SET POINT
---- MAINTENANCE ----
Unit
F
Present Time
12:30P
BACK SELECT
--- SENSOR TRIM ----
System Trim
+0 F
Outdoor Trim +0 F
Return Trim
+0 F
DHW Trim
+0 F
BACK SELECT
Sys=120 F
10:00AM
BACK NEXT
S8 V1.00
Outdoor reset
Heating-BreakOnRise
Day/Night Schedule
DHW Parallel
BACK SELECT
CAUTION
To be able to change the S8 settings
the Program/Run Switch must be set to
Program. The switch is located under
the Enclosure Wiring Cover for security.
The Enclosure Wiring Cover can be
securely closed using a padlock.
STARTUP
MAINTENANCE