Cooling and Heating Troubleshooting Chart (cont)

SYMPTOM

CAUSE

REMEDY

Excessive head
pressure.

Dirty air filter

Replace filter.

Dirty indoor or outdoor coil

Clean coil.

Refrigerant overcharged

Recover excess refrigerant.

Air in system

Recover refrigerant, evacuate system, and recharge.

(Heat) Indoor air restricted or recirculating

Determine cause and correct.

Indoor or outdoor air restricted or
air short-cycling

Determine cause and correct.

Head pressure too low.

Low refrigerant charge

Check for leaks, repair and recharge.

Compressor valves leaking

Replace compressor.

Restriction in liquid tube

Remove restriction.

Excessive suction
pressure.

(Heat) Outdoor coil frosted

Move timer on control board to 30 minutes
between defrost cycles.

(Cool) High heat load

Check for source and eliminate.

Compressor valves leaking

Replace compressor.

Reversing valve hung up or leaking internally

Replace valve.

Refrigerant overcharged

Recover excess refrigerant.

Suction pressure too
low.

(Cool) Dirty air filter

Replace filter.

(Heat) Outdoor coil frosted

Move timer on control board to 30 minutes
between defrost cycles.

Low refrigerant charge

Check for leaks, repair and recharge.

Metering device or low side restricted

Remove source of restriction.

(Cool) Insufficient coil airflow

Increase air quantity. Check filter — replace if
necessary.

(Cool) Temperature too low in conditioned area

Reset thermostat.

(Cool) Outdoor ambient below 40 F

Install low-ambient kit.

Field-installed filter drier restricted

Replace.

Compressor runs but
outdoor fan does not.

Normally closed contacts on defrost board open

Check condition of relay on board. Replace if necessary.

19