Table 3 — Electrical Data
UNIT
50ZH
NOMINAL
V-PH-Hz
IFM
TYPE
VOLTAGE
RANGE
COMPRESSOR
OFM
FLA
IFM
FLA
HEATER
PACKAGE NO.
ELECTRIC
HEAT
POWER
SUPPLY
DISCONNECT
SIZE
Min
Max
RLA
LRA
Nominal
kW*
FLA
MCA
MOCP
FLA
LRA
024
208/230-1-60
Std
187
254
12.8
63.0
0.9
2.4
None
—
—
19.3/ 19.3
25/ 25†
19/ 19
70/ 70
CPHEATER026A00
3.8/ 5.0 18.3/20.8
42.2/ 45.3
45/ 50†
40/ 42
89/ 91
CPHEATER024A00
7.5/10.0 36.1/41.7
64.4/ 71.4
70/ 80
60/ 66
107/112
030
208/230-1-60
Std
187
254
14.4
73.0
1.5
2.4
None
—
—
21.9/ 21.9
30/ 30†
21/ 21
83/ 83
CPHEATER026A00
3.8/ 5.0 18.3/20.8
44.8/ 47.9
45/ 50†
42/ 45 101/103
CPHEATER024A00
7.5/10.0 36.1/41.7
67.0/ 74.0
70/ 80
63/ 69
119/124
CPHEATER040A00
11.3/15.0
54.3/62.5
89.8/100.0
90/110
83/ 93 137/145
036
208/230-1-60
Std
187
254
17.7
93.0
1.5
2.8
None
—
—
26.4/ 26.4
35/ 35†
25/ 25 103/103
CPHEATER026A00
3.8/ 5.0 18.3/20.8
49.3/ 52.4
50/ 60†
46/ 49 121/123
CPHEATER024A00
7.5/10.0 36.1/41.7
71.6/ 78.6
80/ 80
67/ 73 139/144
CPHEATER040A00
11.3/15.0
54.3/62.5
94.3/104.6
100/110
88/ 97 157/165
208/230-3-60
Std
187
254
10.3
77.0
1.5
2.8
None
—
—
17.2/ 17.2
20/ 20†
17/ 17
87/ 87
CPHEATER029A00
3.8/ 5.0 10.5/12.0
30.3/ 32.2
35/ 35†
29/ 31
97/ 99
CPHEATER030A00
7.5/10.0 20.8/24.1
43.2/ 47.3
45/ 50†
41/ 45
107/111
CPHEATER032A00
11.3/15.0
31.4/36.1
56.4/ 62.3
60/ 70
53/ 58
118/123
042
208/230-1-60
Std
187
254
21.5
103.0
1.5
2.8
None
—
—
31.2/ 31.2
40/ 40†
30/ 30
113/113
CPHEATER026A00
3.8/ 5.0 18.3/20.8
54.1/ 57.2
60/ 60†
51/ 54 131/133
CPHEATER024A00
7.5/10.0 36.1/41.7
76.3/ 83.3
80/ 90
71/ 78 149/154
CPHEATER040A00
11.3/15.0
54.3/62.5
99.1/109.3
100/110
92/102 167/175
CPHEATER028A00 15.0/20.0 72.1/83.3 121.3/135.3 125/150
113/125
185/196
208/230-3-60
Std
187
254
12.4
88.0
1.5
2.8
None
—
—
19.8/ 19.8
25/ 25†
19/ 19
98/ 98
CPHEATER029A00
3.8/ 5.0 10.5/12.0
32.9/ 34.8
35/ 35†
31/ 33
108/110
CPHEATER030A00
7.5/10.0 20.8/24.1
45.8/ 49.9
50/ 50†
43/ 47
118/122
CPHEATER032A00
11.3/15.0
31.4/36.1
59.1/ 64.9
60/ 70
55/ 61 129/134
CPHEATER041A00 15.0/20.0 41.6/48.1
71.8/ 79.9
80/ 80
67/ 75 139/146
048
208/230-1-60
Std
187
254
28.2
129.0
1.5
4.2
None
—
—
41.0/ 41.0
50/ 50†
39/ 39 143/143
CPHEATER038A00
3.8/ 5.0 18.3/20.8
63.8/ 67.0
70/ 70
60/ 63 161/163
CPHEATER024A00
7.5/10.0 36.1/41.7
86.1/ 93.1
90/100
81/ 87 179/184
CPHEATER040A00
11.3/15.0
54.3/62.5
108.8/119.1
110/125
101/111
197/205
CPHEATER028A00 15.0/20.0 72.1/83.3 131.1/145.1 150/150
122/135 215/226
208/230-3-60
Std
187
254
13.5
99.0
1.5
4.2
None
—
—
22.6/ 22.6
30/ 30†
22/ 22
113/113
CPHEATER029A00
3.8/ 5.0 10.5/12.0
35.7/ 37.6
40/ 40†
34/ 36 123/125
CPHEATER030A00
7.5/10.0 20.8/24.1
48.6/ 52.7
50/ 60†
46/ 50 133/137
CPHEATER032A00
11.3/15.0
31.4/36.1
61.8/ 67.7
70/ 70
58/ 64 144/149
CPHEATER041A00 15.0/20.0 41.6/48.1
74.6/ 82.7
80/ 90
70/ 77 154/161
060
208/230-1-60
Std
187
254
27.7
170.0
3.1
6.2
None
—
—
43.9/ 43.9
60/ 60†
43/ 43 192/192
CPHEATER038A00
3.8/ 5.0 18.3/20.8
66.8/ 69.9
70/ 70
64/ 66 210/213
CPHEATER024A00
7.5/10.0 36.1/41.7
89.1/ 96.1
90/100
84/ 91 228/233
CPHEATER040A00
11.3/15.0
54.3/62.5
111.8/122.1
125/125
105/114
246/254
CPHEATER028A00 15.0/20.0 72.1/83.3 134.1/148.1 150/150
125/138 264/275
208/230-3-60
Std
187
254
15.9
124.0
3.1
6.2
None
—
—
29.2/ 29.2
35/35†
29/ 29 146/146
CPHEATER029A00
3.8/ 5.0 10.5/12.0
42.3/ 44.2
45/45†
41/ 43 156/158
CPHEATER030A00
7.5/10.0 20.8/24.1
55.2/ 59.3
60/60†
53/ 57 167/170
CPHEATER032A00
11.3/15.0
31.4/36.1
68.4/ 74.3
70/80
65/ 70 177/182
CPHEATER041A00 14.9/19.9 41.4/47.9
80.9/ 89.1
90/90
77/ 84 187/194
460-3-60
Std
414
508
8.0
60.0
1.5
3.2
None
—
—
14.7
20†
15
68
CPHEATER034A00
5.0
6.0
22.2
25†
22
74
CPHEATER035A00
10.0
12.0
29.7
30†
28
80
CPHEATER036A00
15.0
18.0
37.2
40†
35
86
CPHEATER037A00
20.0
24.1
44.8
45†
42
93
LEGEND
FLA
— Full Load Amps
HACR
— Heating, Air Conditioning and Refrigeration
IFM
— Indoor-Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor-Fan Motor
RLA
— Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v or 480 v. If
power distribution voltage to unit varies from rated heater voltage, heater kW
will vary accordingly.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
and equipment (refer to NEC Articles 430 and 440), the overcurrent pro-
tective device for the unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.
Use the following formula to determine the percentage of voltage
imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 240-3-60
AB = 235 v
BC = 242 v
AC = 236 v
235 + 242 + 236
Average voltage =
3
= 238
Determine maximum deviation from average voltage:
(AB) 238 − 235 = 3 v
(BC) 242 − 238 = 4 v
(AC) 238 − 236 = 2 v
Maximum deviation is 4 v.
Determine percentage of voltage imbalance:
4
% Voltage imbalance = 100 x
238
= 1.68%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%
contact your local electric utility company immediately.