Main electronics (scada, rtu and hmi), Rheovac multi-sensor probe (msp) – Intek RheoVac CMS User Manual
Page 7

September 2013
3
© Intek, Inc. 2013
Revision D
1.3 TECHNICAL SPECIFICATIONS – check custom page to determine which
components apply to your CMS
1.3.1 Main Electronics (SCADA, RTU and HMI)
Input Power:
100-250 VAC, 50/60 Hz (UPS recommended)
Digital Communication:
TCP/IP:
Windows File Share (SMB)
OPC
Modbus
Web Interface
Wireless (optional)
All TCP/IP options are enabled by default
Serial:
RS-232 (Modbus) (optional)
Analog Communication:
4-20mA signals (optional)
Temperature Environment:
Operating: 40 to 120°F (5 to 49°C)
Storage: -20 to 158°F (-29 to 70°C)
Local Display (optional):
LCD Screen
or
2 x 20 alphanumeric LCD – displays output parameters and diagnostic messages
Parameter scrolling
Wireless Handheld Tablet (optional)
1.3.2 RheoVac Multi-Sensor Probe (MSP)
Typical Calibration Accuracy:
±5% of total mass flow
Repeatability:
±1.5% of reading
Operating Temperature:
Electronics: 40 to 120°F (5 to 49°C)
Probe: 40 to 158°F (5 to 70°C)
Never subject probe to temperatures above 210°F (99°C)
(high temperature protection optional, up to 450°F)
Operating Pressure:
0.5 to 10 inches Hg absolute
15 psia maximum
Storage Temperature:
-20 to 185°F (-29 to 85°C)
Storage Pressure:
15 psig (maximum)
Process Connection:
Ball valve assembly (1½" thread-o-let must be welded to pipe for installation)
Wetted Surface:
300 Series SS and engineered plastic (depending on model)