Common Electric Heater Calculations

Conversion:
1 KW = 3413

Load Requirement:
KW = (CFM x Temperature Rise) / 3160

Line Current (3 Phase):
Amperage = (KW x 1000) / (Volts x 1.73)

Line Current (1 Phase):
Amperage = (KW x 1000) / Volts

Applied vs. Rated KW Factors
Rated
Voltage

Applied Voltage
200

208

220

230

240

440

460

480

208

.92

1.00

1.12

1.22

1.33

460

.91

1.00

1.09

480

.84

.92

1.00