FloAire STAGED ELECTRIC HEAT MODULE User Manual
Page 18

18
Modulating Coil Thermostat Dip Switch Settings
To test and verify all coil circuits during startup, perform the following:
•
Discharge Control: Disconnect one wire to the discharge air sensor to simulate a call for
maximum amperage.
•
Space Control: Set the Thermostat dipswitches to discharge control.
Once maximum amperage is achieved and tested, configure wiring and dipswitches to their original state.
Step Controller Coil Thermostat Dip Switch Settings
C1025
Thermostat*
C1025-1000
Thermostat*
T920D-F
Thermostat*
Discharge Control
Discharge Control
Discharge Control
S1
On
S1
On
S1
On
S2
Off
S2
Off
S2
Off
S3
Off
S3
Off
S3
On
Space Heating
Space Heating
Space Heating
S1
Off
S1
Off
S1
Off
S2
On
S2
On
S2
On
S3
Off
S3
Off
S3
On
Step Controller and Thermostat Dip Switch Setting Chart
Thermostat
Step Controller
Input
Step Controller Control
Discharge
Control
S1
Off
S1
On
4 Stage Heating
S1
On
S2
Off
S2
Off
S3
On
S2
Off
S3
Off
S4
On
S4
On
2 Stage Heating
Space Heating
S3
On
5 Stage Heating
S1
Off
S4
Off
S3
Off
S2
On
S4
Off
3 Stage Heating
S5
On
S3
Off
S6
Off
S4
On
8 Stage Heating
S3
On
S4
On
S5
On
S6
Off