Every 3 months, Yearly – FloAire STAGED ELECTRIC HEAT MODULE User Manual
Page 22

22
Every 3 months
1. Belt tension should be checked quarterly. See instructions in the previous maintenance section.
Over-tightening will cause excessive bearing wear and noise. Too little tension will cause
slippage at startup and uneven wear.
2. Filters need to be cleaned and/or replaced quarterly, and more often in severe conditions.
Washable filters can be washed in warm soapy water. When re-installing filters, be sure to install
with the airflow in the correct direction as indicated on the filter.
3. Inspect the electric coil. All elements should be in the proper location and clean. If an element is
missing or broken, replace coil immediately.
Filter Quantity Chart
Intake
16” x 20”
20” x 25”
Size 1 Sloped
3
Size 2 Sloped
3
Size 3 Sloped
6
Size 4 Sloped
10
Size 5 Sloped
8
Size 1 V-Bank
3
Size 2 V-Bank
8
Size 3 V-Bank
8
Size 4 V-Bank
15
Size 5 V-Bank
12
Yearly
1. Inspect bearings for wear and deterioration. Replace if necessary.
2. Inspect belt wear and replace torn or worn belts.
3. Inspect bolts and set screws for tightness. Tighten as necessary.
4. Inspect for cleanliness. Clean exterior surfaces only. Remove dust and grease from the motor
housing to ensure proper motor cooling. Remove dirt and grease from the wheel and housing to
prevent imbalance and damage.
5. Inspect the electric coil. All elements should be in the proper location and clean. If an element is
missing or broken, replace coil immediately.