EVCO EC6295S001 User Manual
Page 3
![background image](/manuals/675654/3/background.png)
Evco S.r
.l. • EC 6-295 P220 S001 • Sheet 2/3
8
ALARMS
8.1 Alarms
INDICAT.
every 2 s
Evaporator fan LED
if it is lighted, the evaporator fan will be ON
if it flashes, the after dripping evaporator fan delay will be running (look
at the parameter F5)
Cabinet light LED
if it is lighted, the cabinet light will be ON
if it flashes, the multifunction input will be active (look at the parameters
i0, i1 and i7)
Lock input/thermal protection LED
if it is lighted, there will have been a number of lock input/thermal pro-
tection alarms such as to give the lock of the instrument (turn the instru-
ment OFF and turn it ON again, look at the parameters i2, i3, i4 and i5)
if it flashes, the lock input/thermal protection will be active (look at the
parameters i2, i3, i4 and i5)
ON STAND-BY LED
if it is lighted, the instrument will be in the STAND-BY mode
if it flashes, the instrument will be set as slave but it will not be author-
ized to implement the remote controls coming from the master (look at
the parameter n3)
if it flashes every two seconds, the instrument will be set as slave and
among the remote controls, coming from the master, the slave has to
implement, there will be the turning ON and OFF (look at the param-
eter nA)
MEANING
the instrument will be set as slave and among the remote controls, com-
ing from the master, the slave has to implement, there will be the com-
pressor status (look at the parameter nA).
If you have to show the cabinet temperature, press
the instrument will be set as slave, among the remote controls, coming
from the master, the slave has to implement, there will be the compres-
sor status but there will not be the turning ON and OFF, both the master
and the slave will be in the STAND-BY mode (look at the parameter nA).
If the master is in the STAND-BY mode and the slave is ON, the indica-
tion will be showed alternated with the cabinet temperature
CODE
corrupted
memory
data
person
into the
cabinet
(you can
not
silence
the
buzzer)
lock
input/
thermal
protection
alarm
cabinet
probe
alarm
REASONS
there is the corruption
of the configuration
data of the memory of
the instrument
the lock input/thermal
protection and the
multifunction input are
active
the lock input/thermal
protection is active.
If there has been a
number of lock input/
thermal protection
alarms such as to give
the lock of the instru-
ment,
for 3 s
every 4
(if you
have to restore the
normal operation, turn
the instrument OFF
and turn it ON again)
• the kind of cabinet
probe you have con-
nected is not right
• the cabinet probe
plays up
REMEDIES
switch off the power
supply of the instru-
ment: unless the alarm
disappears, you will
have to change the
instrument
• deactivate the inputs
(look at the param-
eters i0, i1, i2, i3, i4
and i5)
• turn the instrument
OFF and turn it ON
again
• deactivate the input
(look at the param-
eters i2, i3, i4 and i5)
• turn the instrument
OFF and turn it ON
again
• look at the param-
eter /0
• test the integrity of
the probe
• test the instrument-
probe connection
EFFECTS
• you can not gain
access the setting
procedures
• all outputs will be
forced OFF
• the compressor will
be forced OFF
• if the defrost is run-
ning, it will immedi-
ately end
• the defrost will
never be activated
• you will get the ac-
tion you have cho-
sen with the param-
eter i0
• the compressor will
be forced OFF
• if the defrost is run-
ning, it will immedi-
ately end
• the defrost will
never be activated
• the compressor will
work in accordance
with the parameters
C5 and C6
nA
0
15
---
0
remote control the slave has to implement (0 = no controls, 1 and 9 = compressor status,
2 and 10 = defrost activation, 3 and 11 = compressor status and defrost activation,
4 and 12 = turning ON and OFF, 5 and 13 = compressor status and turning ON and OFF,
6 and 14 = defrost activation and turning ON and OFF, 7 and 15 = compressor status,
defrost activation and turning ON and OFF, 8 = reserved)
(19)
LABEL MIN. MAX. U.M.
DEF. ENERGY SAVING (the working setpoint becomes r8)
Hr1
0.0
23.5 h.damin
(6)
0.0
Energy Saving cycle activation time
Hr2
0.0
23.5 h.damin
(6)
0.0
Energy Saving cycle length
LABEL MIN. MAX. U.M.
DEF. REAL TIME DEFROST
Hd1 0.0
23.5 h.damin
(6)
- - -
first defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
Hd2 0.0
23.5 h.damin
(6)
- - -
second defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
Hd3 0.0
23.5 h.damin
(6)
- - -
third defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
Hd4 0.0
23.5 h.damin
(6)
- - -
fourth defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
Hd5 0.0
23.5 h.damin
(6)
- - -
fifth defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
Hd6 0.0
23.5 h.damin
(6)
- - -
sixth defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
(5)
the unit of measure depends on the parameter /8
(6)
damin = 10 minutes
(7)
unless the evaporator temperature is below the defrost end temperature you have set with the parameter d2, the defrost will not be activated
(8)
if the time the compressor is ON is lower than 30 s, the compressor will never be ON; if the cabinet probe failure takes place during a compressor delay, the compressor will be
forced OFF for 1 min; the parameter C1 sets the minimum delay between the end of the cabinet probe failure and the following activation of the compressor (if the parameter
C1 has value 0, the compressor will be forced off for 2 min)
(9)
if at the moment of the defrost activation the cabinet temperature is below the value “working setpoint + r0” , the instrument will not show temperatures above that value; if
at the moment of the defrost activation the cabinet temperature is above the value “working setpoint + r0” , the instrument will not show the increases of the temperature (if
the increase takes place below the value “working setpoint + r0” , look at the previous case); the instrument restores the normal operation once the after dripping evaporator
fan delay ends and the cabinet temperature falls below the freeze temperature
(10) if at the moment of the defrost activation the compressor is ON since a time lower than the one you have set with the parameter, the compressor will be forced ON for a time
such as to finish the time you have set with the parameter
(11) if the lower temperature alarm takes place during the count of the delay, this last will be cleared
(12) if the temperature alarm does not disappear at the end of the times you have set with the parameters A3 and AA, it will further be excluded for the time you have set with the
parameter A6; if the temperature alarm takes place during the defrost and does not disappear at the end of the time you have set with the parameter A7, it will further be
excluded for the time you have set with the parameter A6; if the temperature alarm takes place during the multifunction input activation, it will be excluded for the time
"A5 + A6" since the input activation or for the time you have set with the parameter A6 since the input deactivation
(13) the evaporator fan stop temperature is “cabinet temperature - F1” ; you always have to consider the parameter F1 with positive sign
(14) the instrument will automatically verify the maximum value of the parameter; it always has to be lower than the value you have set with the parameter i4
(15) when there is 1 min to the end of the time you have set with the parameter, the cabinet light will be turned OFF just for 1 s; press
during the time you have set with the
parameter to turn the cabinet light ON and to exclude the function, press
again before the end of the time you have set with the parameter to recover the function
(if the remaining time of the parameter is higher than 1 min, the time will be forced at 1 min and the cabinet light will be turned OFF just for 1 s)