EVCO EC6190 User Manual

Page 3

background image

Every Contr

ol S.r

.l. • EC 6-190 • Sheet 2/2

The instrument shows the indications above flashing and the buzzer utters an intermit-

tent beep.

7

TECHNICAL DATA

7.1 Technical data

Box: self-extinguishing grey.

Size: 53 x 90 x 58 mm (2.08 x 3.54 x 2.28 in, 3 DIN modules).

Installation: on DIN rail (it is not supplied by the builder).

Frontal protection: IP 40.

Connections: screw terminal blocks with pitch 5 mm (0.19 in) for cables up to

2.5 mm² (0.38 sq in, power supply, inputs and outputs), 5 poles single line female

connector with pitch 2.5 mm (0.09 in, serial port), 3 poles single line male connector

with pitch 2.5 mm (0.09 in, to remote indicator).

Ambient temperature: from 0 to 55 °C (32 to 131 °F, 10 ... 90% of relative humidity

without condensate).

Power supply: 230 Vac, 50/60 Hz, 2 VA (standard model) or 115 Vac, 50/60 Hz, 2 VA

(by request).

Alarm buzzer: included.

Measure inputs: 2 (cabinet and evaporator probe) for PTC or NTC probes.

Working range: from -50 to 99 °C (-58 to 210 °F) for PTC probe, from -40 to 99 °C

(-40 to 210 °F) for NTC probe.

Setpoint range: from -55 to 99 °C (-55 to 99 °F).

Resolution: 1 °C.

Display: one red LED 3-digit display 13.2 mm (0.51 in) high, compressor, evaporator

fan and defrost output status indicators.

Outputs: 4 relays: one 5 A @ 250 Vac relay for one ½ HP @ 230 Vac compressor

control (change-over contact), one 5 A @ 250 Vac relay for evaporator fan control

(NO contact), one 5 A @ 250 Vac relay for defrost system control (NO contact) and one

5 A @ 250 Vac relay for alarms control (the relay will be deactivated during the normal

operation and it will be activated during an alarm condition, change-over contact).

Kind of defrost: electric and hot gas defrost.

Defrost control: defrost interval, defrost end temperature and defrost maximum length

(automatic and by hand).

cabinet

tem-

perature

lower or

upper

tempera-

ture alarm

the cabinet tempera-

ture is outside the limit

you have set with the

parameter A1 or A2

test the temperature

close to the probe

(look at the parameters

A0, A1 and A2)

the alarm output will

be activated

F6

0

1

---

0

kind of evaporator fan stop temperature (it is important if F0 = 0; 0 = absolute evaporator fan

stop temperature, 1 = evaporator fan stop temperature relative to the cabinet

temperature)

(5)

LABEL MIN. MAX. U.M.

DEF. SERIAL NETWORK (EVCOBUS)

L0

---

---

---

---

reserved

L1

1

15

---

1

instrument address

(2)

the unit of measure depends on the parameter db

(3)

unless the evaporator temperature is below the defrost end temperature you have set with the parameter d2, the defrost will not be activated

(4)

the instrument restores the normal operation once the dripping ends and the cabinet temperature gets the working setpoint

(5)

the evaporator fan stop temperature is “cabinet temperature - F1” ; you always have to consider the parameter F1 with positive sign.

Serial port: TTL with EVCOBUS communication protocol, adapt for serial interface

EC IFC 02 (for the configurer/cloner system CLONE and supervision system RICS).