WORKING SETPOINT SETTING
The working setpoint is programmable within the lim-
its established with the parameters r1 and r2.
To modify the working setpoint value:
a) keep pushed the key
•
the instrument displays the actual value
•
the comp LED flashes quickly
b) push and release the key
or
as long
as the instrument displays the desired value
•
the working setpoint value gets increased or decreased
c) after the modify release the key
last
•
the instrument automatically turns out from the working
setpoint setting procedure.
CONFIGURATION PARAMETERS SETTING
Configuration parameters are arranged on two levels.
To gain access to the first level:
a) keep pushed for four seconds at least the keys
and
•
passed four seconds the instrument displays the label
PA
To select a parameter:
a) push and release the key
or
as long
as the instrument displays the label of the de-
sired parameter
To modify a parameter value:
a) keep pushed the key
•
the instrument displays the actual value
b) push and release the key
or
as long
as the instrument displays the desired value
•
the parameter value gets increased or decreased
c) after the modify release the key
last
•
the instrument displays the label of the parameter again
To gain access to the second level:
a) enter inside the first level and select the label
PA
b) keep pushed the key
•
the instrument displays the actual value
c) push and release the key
or
as long
as the instrument displays -19
•
the label value gets increased or decreased
d) after the modify release the key
last
•
the instrument displays the label PA again
e) keep pushed for four seconds at least the keys
and
•
passed four seconds the instrument displays the first pa-
rameter of the second level
To turn out from the configuration parameters
setting procedure:
a) keep pushed for four seconds at least the keys
and
or do not operate with the keys
for fifty seconds at least.
ENGLISH
EC 3-180
EC 3-180
EC 3-180
EC 3-180
EC 3-180