EVCO EC3132 User Manual
Page 4

WORKING SETPOINT
Label Min. Max. U.m. Stand.
Working setpoint
rA1
rA2
°
C
0
first working setpoint
rb1
rb2
°
C
0
second working setpoint
CONFIGURATION PARAMETERS
Label Min. Max. U.m. Stand.
Password
PA
-90
100
---
0
password (§)
Label Min. Max. U.m. Stand.
Kind of regulator
-/0
1
3
---
2
kind of regulator
Label Min. Max. U.m. Stand.
Measure input
/0
01
31
---
(*)
kind of probe
/1
-9
+10
°
C
0
calibration
/2
0
6
---
3
digital filter
/4
0
1
---
0
leading zeroes displaying
/5
0
1
---
1
decimal point
/6
-99
+999 points
-20
lower end of scale for 0/4-20 mA input (it coincides with the mini-
mum calibration value of the transducer)
/7
-99
+999 points
+80
upper end of scale for 0/4-20 mA input (it coincides with the maxi-
mum calibration value of the transducer)
Label Min. Max. U.m. Stand.
ON-OFF temperature regulator associated to the first/
second working setpoint and to the output K 1/K 2
rA0/rb0 -99
+99
°
C
(*)
hysteresis (differential) (§)
rA1/rb1 -99
+999
°
C
(*)
minimum working setpoint programmable
rA2/rb2 -99
+999
°
C
(*)
maximum working setpoint programmable
rA3/rb3
0
1
---
1
“cooling” or “heating” functioning
rA4/rb4
0
1
---
0
kind of hysteresis (kind of differential)
rA5/rb5
0
1
---
0
locking of the working setpoint modification
Label Min. Max. U.m. Stand.
Output K 1/K 2 protection
CA0/Cb0 0
999
sec.
0
disabling time to the output activation from the instrument start
CA1/Cb1 0
999
sec.
0
disabling time to the output activation from the previous activation
CA2/Cb2 0
999
sec.
0
disabling time to the output activation from the previous deactiva-
tion
CA3/Cb3 0
1
---
0
output status during a probe failure alarm
CA4/Cb4 0
1
---
0
disabling time to the output activation and deactivation
Label Min. Max. U.m. Stand.
Temperature alarm regulator associated to the first/sec-
ond temperature alarm
AA0/Ab0 (*)
+99
°
C
(*)
hysteresis (differential)
AA1/Ab1 -99
+999
°
C
0
alarm setpoint
AA3/Ab3 0
999
min.
0
disabling time to the alarm activation from the instrument start
AA4/Ab4 1
7
---
1
kind of alarm
2
3
and
or do not operate with the keys
for fifty seconds at least.