EVCO EC3132 User Manual

Page 4

background image

WORKING SETPOINT

Label Min. Max. U.m. Stand.

Working setpoint

rA1

rA2

°

C

0

first working setpoint

rb1

rb2

°

C

0

second working setpoint

CONFIGURATION PARAMETERS

Label Min. Max. U.m. Stand.

Password

PA

-90

100

---

0

password (§)

Label Min. Max. U.m. Stand.

Kind of regulator

-/0

1

3

---

2

kind of regulator

Label Min. Max. U.m. Stand.

Measure input

/0

01

31

---

(*)

kind of probe

/1

-9

+10

°

C

0

calibration

/2

0

6

---

3

digital filter

/4

0

1

---

0

leading zeroes displaying

/5

0

1

---

1

decimal point

/6

-99

+999 points

-20

lower end of scale for 0/4-20 mA input (it coincides with the mini-

mum calibration value of the transducer)

/7

-99

+999 points

+80

upper end of scale for 0/4-20 mA input (it coincides with the maxi-

mum calibration value of the transducer)

Label Min. Max. U.m. Stand.

ON-OFF temperature regulator associated to the first/

second working setpoint and to the output K 1/K 2

rA0/rb0 -99

+99

°

C

(*)

hysteresis (differential) (§)

rA1/rb1 -99

+999

°

C

(*)

minimum working setpoint programmable

rA2/rb2 -99

+999

°

C

(*)

maximum working setpoint programmable

rA3/rb3

0

1

---

1

“cooling” or “heating” functioning

rA4/rb4

0

1

---

0

kind of hysteresis (kind of differential)

rA5/rb5

0

1

---

0

locking of the working setpoint modification

Label Min. Max. U.m. Stand.

Output K 1/K 2 protection

CA0/Cb0 0

999

sec.

0

disabling time to the output activation from the instrument start

CA1/Cb1 0

999

sec.

0

disabling time to the output activation from the previous activation

CA2/Cb2 0

999

sec.

0

disabling time to the output activation from the previous deactiva-
tion

CA3/Cb3 0

1

---

0

output status during a probe failure alarm

CA4/Cb4 0

1

---

0

disabling time to the output activation and deactivation

Label Min. Max. U.m. Stand.

Temperature alarm regulator associated to the first/sec-

ond temperature alarm

AA0/Ab0 (*)

+99

°

C

(*)

hysteresis (differential)

AA1/Ab1 -99

+999

°

C

0

alarm setpoint

AA3/Ab3 0

999

min.

0

disabling time to the alarm activation from the instrument start

AA4/Ab4 1

7

---

1

kind of alarm

2

3

and

or do not operate with the keys

for fifty seconds at least.