WORKING SETPOINT SETTING
If the parameter -/0 has value 3 the second working
setpoint does not exist.
The first/second working setpoint is programmable
within the limits established with the parameters rA1/
rb1 and rA2/rb2.
If the parameter rA5/rb5 has value 1 the first/second
working setpoint can not be modified as long as the
parameter rA5/rb5 gets set to 0.
To modify the first working setpoint value:

a) keep pushed the key

the instrument displays the actual value

the out 1 flashes quickly

b) push and release the key

or

as long

as the instrument displays the desired value

the first working setpoint value gets increased or de-

creased

c) after the modify release the key

last

the instrument displays the set value.

To modify the second working setpoint value:

a) release and keep pushed the key

during

the flashing of the LED out 1

the instrument displays the actual value

the out 2 flashes quickly

b) push and release the key

or

as long

as the instrument displays the desired value

the second working setpoint value gets increased or de-

creased

c) after the modify release the key

last

the instrument automatically turns out from the working

setpoint setting procedure.

CONFIGURATION PARAMETERS SETTING
Configuration parameters are arranged on two levels.
To gain access to the first level:

a) keep pushed for four seconds at least the keys

and

passed four seconds the instrument displays the label

PA

To select a parameter:

a) push and release the key

or

as long

as the instrument displays the label of the de-
sired parameter

To modify a parameter value:

a) keep pushed the key

the instrument displays the actual value

b) push and release the key

or

as long

as the instrument displays the desired value

the parameter value gets increased or decreased

c) after the modify release the key

last

the instrument displays the label of the parameter again

To gain access to the second level:

a) enter inside the first level and select the label

PA

b) keep pushed the key

the instrument displays the actual value

c) push and release the key

or

as long

as the instrument displays -19

the label value gets increased or decreased

d) after the modify release the key

last

the instrument displays the label PA again

e) keep pushed for four seconds at least the keys

and

passed four seconds the instrument displays the first pa-

rameter of the second level

To turn out from the configuration parameters
setting procedure:

a) keep pushed for four seconds at least the keys

ENGLISH

EC 3-132

EC 3-132

EC 3-132

EC 3-132

EC 3-132

Quick reference

1

4

Label Min. Max. U.m. Stand.

Connection in a serial network with EVCOBUS protocol

communication

L1

1

15

---

1

instrument address

L2

0

7

---

0

instrument group

Additional informations:

• the symbol (§) indicates that the parameter is of the first level
• if the parameter -/0 has value 3 the parameters of the family rB do not exist
• the symbol (*) indicates that the value depends from the measure input presetting requested
• if the instrument is preset to accept at the measure input “J”/”K” thermocouples the parameter /5 does not

exist

• if the instrument is not preset to accept at the measure input 2 and 3 wires 0/4-20 mA temperature

transducers the parameters /6 and /7 do not exist.