Ec 3-132 – EVCO EC3132 User Manual
Page 3

WORKING SETPOINT SETTING
If the parameter -/0 has value 3 the second working
setpoint does not exist.
The first/second working setpoint is programmable
within the limits established with the parameters rA1/
rb1 and rA2/rb2.
If the parameter rA5/rb5 has value 1 the first/second
working setpoint can not be modified as long as the
parameter rA5/rb5 gets set to 0.
To modify the first working setpoint value:
a) keep pushed the key
•
the instrument displays the actual value
•
the out 1 flashes quickly
b) push and release the key
or
as long
as the instrument displays the desired value
•
the first working setpoint value gets increased or de-
creased
c) after the modify release the key
last
•
the instrument displays the set value.
To modify the second working setpoint value:
a) release and keep pushed the key
during
the flashing of the LED out 1
•
the instrument displays the actual value
•
the out 2 flashes quickly
b) push and release the key
or
as long
as the instrument displays the desired value
•
the second working setpoint value gets increased or de-
creased
c) after the modify release the key
last
•
the instrument automatically turns out from the working
setpoint setting procedure.
CONFIGURATION PARAMETERS SETTING
Configuration parameters are arranged on two levels.
To gain access to the first level:
a) keep pushed for four seconds at least the keys
and
•
passed four seconds the instrument displays the label
PA
To select a parameter:
a) push and release the key
or
as long
as the instrument displays the label of the de-
sired parameter
To modify a parameter value:
a) keep pushed the key
•
the instrument displays the actual value
b) push and release the key
or
as long
as the instrument displays the desired value
•
the parameter value gets increased or decreased
c) after the modify release the key
last
•
the instrument displays the label of the parameter again
To gain access to the second level:
a) enter inside the first level and select the label
PA
b) keep pushed the key
•
the instrument displays the actual value
c) push and release the key
or
as long
as the instrument displays -19
•
the label value gets increased or decreased
d) after the modify release the key
last
•
the instrument displays the label PA again
e) keep pushed for four seconds at least the keys
and
•
passed four seconds the instrument displays the first pa-
rameter of the second level
To turn out from the configuration parameters
setting procedure:
a) keep pushed for four seconds at least the keys
ENGLISH
EC 3-132
EC 3-132
EC 3-132
EC 3-132
EC 3-132
Quick reference
1
4
Label Min. Max. U.m. Stand.
Connection in a serial network with EVCOBUS protocol
communication
L1
1
15
---
1
instrument address
L2
0
7
---
0
instrument group
Additional informations:
• the symbol (§) indicates that the parameter is of the first level
• if the parameter -/0 has value 3 the parameters of the family rB do not exist
• the symbol (*) indicates that the value depends from the measure input presetting requested
• if the instrument is preset to accept at the measure input “J”/”K” thermocouples the parameter /5 does not
exist
• if the instrument is not preset to accept at the measure input 2 and 3 wires 0/4-20 mA temperature
transducers the parameters /6 and /7 do not exist.