beautypg.com

EVCO EVRSF205N9VRB User Manual

Page 5

background image

EVCO S.p.A. | Codice 104RSF200E124 | Page 5 of 8 | PT 20/14 | version 1.1

14

WORKING SETPOINT AND CONFIGURATION PARAMETERS

14.1

Working set-point

PARAM.

MIN.

MAX.

U.M.

EVRSF204 EVRSF205 WORKING SETPOINT

r1

r2

°C/°F (1)

-18,0

-18,0

working set-point; see also r0

14.2

Configuration parameters

PARAM.

MIN.

MAX.

U.M.

EVRSF204 EVRSF205 WORKING SETPOINT

SP

r1

r2

°C/°F (1)

-18,0

-18,0

working set-point; see also r0

PARAM.

MIN.

MAX.

U.M.

EVRSF204 EVRSF205 MEASUREMENT INPUTS

CA1

-25

25,0 °C/°F (1)

0,0

0,0

offset cell probe

CA2

-25

25,0 °C/°F (1)

0,0

0,0

offset evaporator probe

CA3

-25

25,0 °C/°F (1)

0,0

0,0

offset condenser probe

P0

0

1

- - -

1

1

probe type
0

=

PTC

1

=

NTC

P1

0

1

- - -

1

1

degree Celsius decimal point (during normal operation)
1

=

YES

P2

0

1

- - -

0

0

temperature unit of measurement (2)
0

=

°C

1

=

°F

P3

0

2

- - -

1

1

evaporator probe function
0

=

probe absent

1

=

defrosting probe and probe for evaporator fan thermostating

2

=

probe for evaporator fan thermosatating

P4

0

1

- - -

1

1

third input function
0

=

digital input (micro switch/multi-function input 1)

1

=

analogue input (condenser probe)

P8

0

250

0.1 s

5

5

delay displaying temperature variation detected by the probes

PARAM.

MIN.

MAX.

U.M.

EVRSF204 EVRSF205 MAIN REGULATOR

r0

0,1 (3)

15,0 °C/°F (1)

2,0

2,0

working set-point differential

r1

-99

r2

°C/°F (1)

-50

-50

minimum working set-point

r2

r1

99,0 °C/°F (1)

50,0

50,0

maximum working set-point

r3

0

1

- - -

0

0

locking of working set-point calibration (using the procedure described in paragraph 10.1)
1

=

YES

r4

0,0

99,0 °C/°F (1)

0,0

0,0

increase in temperature during “energy saving” function; see also i0, i5 and i10

r5

0,0

99,0 °C/°F (1)

0,0

0,0

decrease in temperature during “overcooling” function; see also r6

r6

0

240

min

30

30

duration of “overcooling” function; see also r5

PARAM.

MIN.

MAX.

U.M.

EVRSF204 EVRSF205 COMPRESSROR PROTECTION SYSTEM

C0

0

240

min

0

0

delay in switching on of compressor after the device switches on (4)

C1

0

240

min

5

5

minimum time between two consecutive compressor start-ups; also delay in compressor start-up after conclusion of cell probe
error (code “Pr1”) (5) (6)

C2

0

240

min

3

3

minimum compressor switch-off duration; see also C18 (5) (7)

C3

0

240

s

0

0

minimum duration of compressor switch on time

C4

0

240

min

10

10

duration of compressor switch off during cell probe error (code “Pr1”); see also C5

C5

0

240

min

10

10

duration of compressor switch on during cell probe error (code “Pr1”); see also C4

C6

0,0

199

°C/°F (1)

80,0

80,0

condenser temperature is higher than that at which the condenser overheating alarm is activated (code “COH”) (8)

C7

0,0

199

°C/°F (1)

90,0

90,0

condenser temperature above which the blocked compressor alarm is activated (“CSd” code)

C8

0

15

min

1

1

blocked compressor alarm delay (“CSd” code) (9)

C10

0

999

10 h

0

0

number of operating hours is higher than the limit at which the need for maintenance is signalled.
0

=

function absent

C11

0

240

s

3

3

compressor 2 switch-on delay from compressor 1 switch-on (only if u1 and/or u11 = 7) (10)

PARAM.

MIN.

MAX.

U.M.

EVRSF204 EVRSF205 DEFROSTING

d0

0

99

h

8

8

if d8 = 0, 1 or 2, defrosting interval (11)
0

=

interval defrosting will never be activated

if d8 = 3, maximum defrost interval

d1

0

2

- - -

0

0

type of defrosting
0

=

ELECTRIC - during defrosting the compressor will remain off and the defrosting output will be activated; evaporator fan
activity will depend on parameter F2

1

=

BY HOT GAS - during defrosting the compressor will be switched on and the defrosting output will be activated;
evaporator fan activity will depend on parameter F2

2

=

VIA STOPPING OF COMPRESSOR - during defrosting the compressor will remain switched off and the defrosting output
will remain deactivated; evaporator fan activity will depend on parameter F2

d2

-99

99,0 °C/°F (1)

2,0

2,0

temperature at end of defrosting (only if P3 = 1); see also d3

d3

0

99

min

30

30

se P3 = 0 or 2, defrosting duration
se P3 = 1, maximum defrosting duration; see also d2
0

=

defrosting will not be activated

d4

0

1

- - -

0

0

defrosting on device switch-on (4)
1

=

YES

d5

0

99

min

0

0

if d4 = 0, minimum time between switching on of device and activation of defrosting; see also i0 and i5 (4)
if d4 = 1, delay in activation of defrosting after device is switched on ; see also i0 and i5 (4)

d6

0

1

- - -

1

1

temperature displayed during defrosting
0

=

cell temperature

1

=

if at the time of defrosting activation, the cell temperature is lower than the “working set-point + r0”, at most “working
set- point + r0”; if at the time of defrosting activation, the cell temperature is higher than the “working set-point + r0”,
at most the cell temperature when defrosting is activated (12)

d7

0

15

min

2

2

dripping duration (during dripping the compressor will remain switched off and the defrosting output will remain deactivated; if
d16 = 0, evaporator fan activity will depend on parameter F2; if d16 ≠ 0, the evaporator fan will remain switched off)

d8

0

3

- - -

0

0

defrosting activation methods
0

=

AT INTERVALS - defrosting will be activated once the device has altogether been running for time d0

1

=

AT INTERVALS - FOR COMPRESSOR SWITCH-ON - defrosting will be activated once the compressor has altogether been
switched on for time d0

2

=

AT INTERVALS - FOR EVAPORATOR TEMPERATUREE - defrosting will be activated when the evaporator temperature
has remained below the temperature d9 for a total time of d0 (13)

3

=

ADAPTABLE - defrosting will be activated at intervals, whose duration will each time depend on the duration of
compressor switch-ons and the evaporator temperature; see also d18, d19 and d22 (13)

d9

-99

99,0 °C/°F (1)

0,0

0,0

evaporator temperature is higher than that at which the defrost interval counter is suspended (only if d8 = 2)

d11

0

1

- - -

0

0

defrosting alarm switches off once maximum time limit has been reached (code “dFd”; only if P3 = 1 and in absence of an
evaporator probe (code “Pr2”)
1

=

YES

d15

0

99

min

0

0

minimum time that the compressor must be switched on before defrosting can be activated (only if
d1 = 1) (14)

This manual is related to the following products: