EVCO EVRSF205N9VRB User Manual

Page 2

background image

EVCO S.p.A. | Codice 104RSF200E124 | Page 2 of 8 | PT 20/14 | version 1.1

3.4

Evaporator temperature display

1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Hold the key down for 1 s: the display will show the
first label available.

3.

Press and release the key or the key to select
Pb2”.

4.

Press and release the key .

To exit the procedure:
5.

Press and release the

key or do not operate for

60 sec.

6.1 Press and release the or key until the display

shows the cell temperature or do not operate for 60
sec.

Alternatively:
6.2 Press and release the key.
If the evaporator probe is absent (parameter P3 = 0), the
label “Pb2” will not be displayed.
3.5

Condenser temperature display

1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Hold the key down for 1 s: the display will show the
first label available.

3.

Press and release the key or the key to select
Pb3”.

4.

Press and release the key.

To exit the procedure:
5.

Press and release the

key or do not operate for

60 sec.

6.1 Press and release the or key until the display

shows the cell temperature or do not operate for 60
sec.

Alternatively:
6.2 Press and release the key.
If the third input function is that of the digital input (param-
eter P4 = 0), the label “Pb3” will not be displayed.
3.6

Activation/deactivation of “overcooling”
function

1.

Make sure that the keyboard is not locked and that no
other operation is in progress, that defrosting and/or
dripping is not in progress and that the evaporator fan
is off.

2.

Hold the key down for 4 s: the Overcooling LED will
light up.

During the “overcooling” function the working setpoint is
reduced by the temperature established with parameter r5;
the operation lasts for the amount of time established with
parameter r6.
During “overcooling” defrosting is never activated; if
the defrosting interval expires when the function is in
progress, defrosting will be activated at the end of the
function.
3.7

Defrosting activation in manual mode

1.

Make sure that the keyboard is not locked and that no
other operation is in progress; ensure that the
“overcooling” function is not in progress

2.

Hold the key down for 4 s.

If the evaporator probe function is that of the defrosting
probe (parameter P3=1) and upon activation of defrosting,
the temperature of the evaporator is higher than that estab-
lished with parameter d2, the defrosting function will not be
activated.
3.8

Switch-on/off of the cell light in manual
mode (only if parameter u1
and/or parameter u11 is set at 0)

1.

Make sure no procedures are in progress

2.

Press and release the

key: the “AUX” LED will

switch on/off.

Using the door digital inputs it is also possible to switch on/
off the cell light by remote; see also parameter u2.
If parameter u1 is set at 0 (i.e. the utility managed by the
fourth output is the cabinet light) and parameter u11 is set
at 2 (i.e. the utility managed by the fifth output is the
auxiliary output), holding the key down for 2 s will cause
the switch-on/off of the “AUX” LED and of the auxiliary
output.
3.9

Demister resistors switch-on (only if the
parameter u1 and/or parameter u11 is set at
1)

1.

Ensure that the device is switched on and that no other
procedure is in progress.

2.

Hold the

key down for 2 s: the “AUX” LED will

light up and the resistors will be switched on, both
for the amount of time established with parameter
u6.

Manually switching off the demisting resistors is not permit-
ted (that is, before the time established with parameter u6
expires).

3.10

Switch-on/off of the auxiliary output in
manual mode (only if parameter u1 and/or
parameter u11 is set at 2)

1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Press and release the

key: the “AUX” LED will

switch on/off.

Using the digital inputs it is also possible to remotely switch
on/off the auxiliary output.
If parameter u1 is set at 2 (i.e. the utility managed by the
fourth output is the auxiliary output) and parameter u11 is
set at 0 (i.e. the utility managed by the fifth output is the
cabinet light), holding the

key down for 2 s will cause

the switch-on/off of the “AUX” LED and of the cabinet
light.
If the auxiliary output has been switched on manually,
then it can also be switched off manually (similarly, if the
auxiliary output has been remotely switched on, then it
can only be switched off in the same manner); see also
parameter u2.
3.11

Locking/unlocking the keyboard

To lock the keyboard:
1.

Make sure no procedures are in progress

2.

Hold the

and

keys down for 1 s:

the display will show “Loc”.

If the keyboard is locked, the following are not permitted:
-

device switch-on/off in manual mode

-

display of evaporator temperature (via the procedure
explained in paragraph 3.4)

-

display of the condenser temperature (via the proce-
dure indicated in paragraph 3.5)

-

activation/deactivation of “overcooling” function

-

manual activation of defrosting

-

manual switch on/off of the auxiliary output

-

activation of operation for low of high percentage of
relative humidity and learning the kind of operation

-

see information regarding the HACCP alarms

-

cancellation of HACCP alarm list

-

display of compressor operation hours

-

cancellation of compressor operation hours

-

changing the working setpoint (with the procedure de-
scribed in 9.1).

The operations cause the display of the label “Loc” per 1
sec.
To unlock the keyboard:
1.

Hold the key and thee

key down for 1 s: the

display will show the message “UnL” for 1 sec.

3.12

Silencing the buzzer

To lock the keyboard:
1.

Make sure no procedures are in progress

2.

Press a key (the first pressing of the key will not cause
the effect associated with that key).

If the parameter u1 and/or the parameter u11 is set at 3
(i.e. the utility managed by the fourth output and/or the
utility managed by the fifth output is the alarm output) and
parameter u4 is set at 1, pressing the key will also cause the
deactivation of the output.
If parameter u9 is set at 0, the buzzer will not be acti-
vated.

4

OPERATION DUE TO LOW OR HIGH RELATIVE
HUMIDITY PERCENTAGE (ONLY IF PARAMETER
F0 IS ISET AT 5)

4.1

Preliminary notes

During operation for low percentage of relative humidity, the
evaporator ventilator will be switched on if the compressor is
switched off (parameter F4 determines the amount of time
it is switched off while parameter F5 determines the amount
of time it is switched on).
During operation for a high percentage of relative humidity
the evaporator fan is always on.
4.2

Activation of operation for low or high
percentage relative humidity in manual
mode.

1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Hold the and keys down for 4 s: the display will
show “rhL” (operation for low percentage of relative
humidity) or “rhH” (operation for high percentage of
relative humidity) for 10 sec.

To restore the normal display before the operation is com-
plete:
3.

Press a key.

Activation of the operation for a low or high percentage of
relative humidity can be done using parameter F6.
If the parameter F0 is not set at 5, pressing the and

keys will cause the display of the “- - -“ indication for

1 s.

4.3

Learning the type of operation in progress

1.

Make sure no procedures are in progress

2.

Press and release the and keys: the display will
show “rhL” (operation for low percentage of relative
humidity) or “rhH” (operation for high percentage of
relative humidity) for 10 sec.

To restore the normal display before the operation is com-
plete:
3.

Press a key.

If parameter F0 is not set at 5, pressing the and keys
will cause:
-

the display of the message “- - - -“ for 1 sec if the
keyboard is not locked

-

display of the label “Loc” for 1 sec if the keyboard is
locked..

5

ENERGY SAVING

5.1

Preliminary notes

Once the time you have set with parameter i10 has passed,
without activations of the door micro switch input (after the
cell temperature has reached the work set-point) the “en-
ergy saving” function is activated (until the input is activated
again).
During function “Energy Saving” the working setpoint is
increased of the temperature you have set with parameter
r4 and the evaporator fan is turned on cyclically, on condition
that parameter F0 has value 1 or 2 (parameter F13 sets the
time the fan remains turned off and parameter F14 the time
it remains turned on).
It is also possible to activate the “energy saving” function in
remote mode through the digital inputs (with effect only on
the compressor).

6

“HACCP” FUNCTION

6.1

Preliminary notes

The device can memorise the following HACCP alarms:
-

minimum temperature alarm (code “AL”)

-

maximum temperature alarm (code “AH”)

-

door micro switch input alarm (code “id”)

The device supplies the following information for every
alarm:
-

the critical value

-

the duration of the alarm (from 1 min to 99 hours and
59 min, partial if the alarm is in progress).

Code Critical value

AL

the minimum temperature of the cell during any
alarm of this type

AH

the maximum temperature of the cell during any
alarm of this type

iD

the maximum cell temperature during any alarm
of this type; see also parameter i4

The device stored the minimum temperature alarm on con-
dition that the temperature associated to the alarm is that of
the cell (parameter A0 = 0).
if the device is switched off, no alarms will be stored.
The device updates the information regarding the the alarms
provided the critical value of the new alarm is more critical
than that stored or provided the information has already
been displayed.
The “HACCP” LED provides information regarding the stor-
age status of the alarms; see paragraph 10.1.
6.2

Display of HACCP alarm information

To begin the procedure:
1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Hold the key down for 1 s: the display will show the
first label available.

3.

Press and release the or key to select “LS”.

4.

Press and release the key: the display will show
one of the codes included in the table in paragraph
6.1.

If the device does not have any alarms stored, the label
LS” will not be displayed.
To select an alarm:
5.

Press and release the

or

key (to select, for

example, “AH”).

To see information regarding the alarm:
6.

Press and release the key: the HACCP LED will stop
flashing and remain on permanently and the display
will show, for example, the following information in
succession (for example):

Inform. Part

8.0

the critical value is 8.0 °C/8 °F

dur

the display is about to show the alarm duration

h01

the alarm lasted for 1 hour (other data continues)

n15

the alarm lasted 1 hour and 15 min

AH

the alarm selected

the displays each piece of information for 1 s.
To exit the information sequence: