EVCO EVRS235N9 User Manual
Page 7
EVCO S.p.A. | Code 104RS235E104 | Page 7 of 10 | PT 07/14 | version 1.0
d4
0
1
- - -
0
0
defrosting when device is switched on (only if d8 = 0, 1, 2 or 3) (4)
1
=
YES
d5
0
99
min
0
0
if d4 = 0, minimum time between switching on of device and activation of defrosting; see also i0 and i5 (4)
if d4 = 1, delay in activation of defrosting after device is switched on ; see also i0 and i5 (4)
d6
0
1
- - -
1
1
temperature displayed during defrosting (only if P5 = 0)
0
=
cabinet temperature or CPT temperature
1
=
if on activation of defrosting, the cabinet temperature or the CPT temperature is below the “work set point + r0”, at
maximum “ work set point + r0”; if on activation of defrosting, the cabinet temperature or the CPT temperature is above
“work set point + r0”, at maximum the cabinet temperature or CPT temperature on activation of defrosting (12)
d7
0
15
min
2
2
dripping duration (during dripping the compressor will remain switched off and the defrosting output will remain deactivated; if d16
= 0, evaporator fan activity will depend on parameter F2; if d16 ¹ 0, the evaporator fan will remain switched off)
d8
0
4
- - -
0
0
defrosting activation methods
0
=
AT INTERVALS - defrosting will be activated once the device has altogether been running for time d0
1
=
AT INTERVALS - FOR COMPRESSOR SWITCH-ON - defrosting will be activated once the compressor has altogether been
switched on for time d0
2
=
AT INTERVALS - FOR EVAPORATOR TEMPERATUREE - defrosting will be activated when the evaporator temperature has
remained below the temperature d9 for a total time of d0 (13)
3
=
ADAPTABLE - defrosting will be activated at intervals, whose duration will each time depend on the duration of compressor
switch-ons and the evaporator temperature; see also d18, d19 and d22 (13)
4
=
IN REAL TIME - (can be set only in EVRS235 model) defrosting will be activated at the times established in parameters Hd1
... Hd6
d9
-99
99,0 °C/°F (1)
0,0
0,0
evaporator temperature is higher than that at which the defrost interval counter is suspended (only if d8 = 2)
d11
0
1
- - -
0
0
defrosting alarm switches off once maximum time limit has been reached (code “dFd”; only if P3 = 1 and in absence of an
evaporator probe (code “Pr2”)
1
=
YES
d15
0
99
min
0
0
minimum time that the compressor must be switched on before defrosting can be activated (only if
d1 = 1) (14)
d16
0
99
min
0
0
predripping duration (during predripping the compressor will remain switched off, the defrosting output will be activated and the
evaporator fan will remain switched off)
d18
0
999
min
40
40
defrosting interval (only if d8 = 3; defrosting will be activated when the compressor has been on totally, with the evaporator
temperature below that of d22, for time d18)
0
=
defrosting will never be activated due to the effect of this condition
d19
0,0
40,0 °C/°F (1)
3,0
3,0
evaporator temperature above which the defrost is activated (relative to the evaporator temperatures average, or “evaporator
temperatures average - d19”) (only if d8 = 3)
d20
0
500
min
180
180
minimum consecutive time the compressor must be switched on such as to provoke the defrost activation
0
=
defrosting will never be activated due to the effect of this condition
d22
0,0
10,0 °C/°F (1)
2,0
2,0
evaporator temperature above which the defrosting interval is suspended (relative to the evaporator temperatures average, or
“evaporator temperatures average + d22”) (only if d8 = 3); also look at d18
d24
0
999
min
30
30
maximum duration of activation of the defrosting synchronisation input due to activation of defrosting (only if i0 = 6)
d25
0
1
- - -
0
0
enabling of the outlet air probe as defrosting probe during the evaporator probe error (code “Pr2”;
only if P4 = 3); see also d26 (15)
1
=
YES
d26
0
99
h
6
6
defrosting interval for effect of enabling of outlet air probe like defrosting probe during evaporator probe error (“Pr2” code; only if
d25 = 1) (11)
0
=
interval defrosting will never be activated
PARAM.
MIN.
MAX.
U.M.
EVRS225 EVRS235 TEMPERATURE ALARMS
A0
0
1
- - -
0
0
temperature associated with the minimum temperature alarm (code “AL”)
0
=
cabinet temperature or CPT temperature
1
=
evaporator temperature (16)
A1
-99
99,0 °C/°F (1) -10,0
-10,0
temperature below that at which the minimum temperature alarm is activated (code “AL”); see also A0, A2 and A11
A2
0
2
- - -
1
1
type of minimum temperature alarm (code “AL”)
0
=
alarm absent
1
=
relative to working set-point (that is “working set-point - A1”; consider A1 without sign)
2
=
absolute (that is A1)
A4
-99
99,0 °C/°F (1) 10,0
10,0
temperature higher than that at which the maximum temperature alarm is activated (code “AH”); see also A5 and A11
A5
0
2
- - -
1
1
type of maximum temperature alarm (code “AH”)
0
=
alarm absent
1
=
relative to working set-point (that is “working set-point + A4”; consider A1 without sign))
2
=
absolute (that is A4)
A6
0
240
min
120
120
delay in maximum temperature alarm (code “AH”) after the device is switched on (4)
A7
0
240
min
15
15
temperature alarm delay(“AL” code and “AH” code)
A8
0
240
min
15
15
delay in maximum temperature alarm (code “AH”) from the conclusion of evaporator fan standstill (17)
A9
0
240
min
15
15
delay in maximum temperature alarm (code “AH”) following the deactivation of the door micro switch input (18)
A10
0
240
min
not avail.
1
duration of a power cut such to cause the power cut alarm to be memorised ( “PF” code)
A11
0,1 (3)
15,0 °C/°F (1)
2,0
2,0
differential of parameters A1and A4
A12
0
2
- - -
not avail.
1
type of power supply cut-off alarm signal (“PF” code);
0
=
alarm will be signalled by the “HACCP” LED
1
=
alarm will be signalled by the “PF” code, the buzzer and the “HACCP” LED
2
=
alarm will be signalled by the “PF” code, buzzer (as long as cut-off duration exceeds time A10) and by the “HACCP” LED
PARAM.
MIN.
MAX.
U.M.
EVRS225 EVRS235 EVAPORATOR FAN AND CONDENSER FAN
F0
0
5
- - -
1
1
evaporator fan activity during normal operation
0
=
switched off
1
=
switched on; see also F13, F14 and i10 (19)
2
=
in parallel with the compressor; see also F9, F13, F14 and i10 (20)
3
=
depending on F1; see also F9, F13 and F14 (22) (23)
4
=
switched off if the compressor is switched off, dependent on F1 if the compressor is switched on; see also F9, F13 and F14
(21) (23)
5
=
with proportional band, see also F20 (it is recommended to set parameter F0 at 5 in case of
F1
-99
99,0 °C/°F (1)
-1,0
-1,0
evaporator temperature above the limit at which the evaporator fan is switched off (only if F0 = 3 or 4); see also F8
F2
0
2
- - -
0
0
evaporator fan activity during defrosting and dripping
0
=
switched off
1
=
switched on (setting parameter d7 to 0 is recommended)
2
=
in case of analogue management, as if F0 = 5
in case of digital management, depending on F0
F3
0
15
min
0
0
maximum duration of evaporator fan deactivation; see also F7 (during evaporator fan deactivation the compressor can be switched
on, the defrosting output will remain deactivated and the evaporator fan will remain switched off)
F7
-99
99,0 °C/°F (1)
5,0
5,0
evaporator temperature below limit at which the evaporator fan is deactivated (relative to working set point, that is “working set
point + F7”); see also F3
F8
0,1 (3)
15,0 °C/°F (1)
2,0
2,0
parameter F1differential
F9
0
240
s
0
0
delay in the switching off of evaporator fan following the switching off of the compressor (only if F0 = 2, 3, 4 and 5)
F11
0,0
99,0 °C/°F (1) 15,0
15,0
temperature of the condenser above which the condenser fan is switched on (“F11 + 2,0 °C/4 °F, only if
u1 and/or u11 = 6) (25) (26)