beautypg.com

Modbus/tcp multi-mode connectivity, Plc master/devicemaster up slave mode, Plc slave/devicemaster up master mode – Comtrol Modbus TCP User Guide User Manual

Page 11

background image

DeviceMaster UP Modbus/TCP User Guide: 2000447 Rev. I

Chapter 1. Introduction - 11

Modbus/TCP Multi-Mode Connectivity

1.4.4. Modbus/TCP Multi-Mode Connectivity

The Modbus/TCP firmware 5.x supports the following Modbus/TCP communication modes:

PLC Master/DeviceMaster UP Slave Mode

on Page 11

PLC Slave/DeviceMaster UP Master Mode

on Page 11

Dual Master (Virtual Peer-to-Peer) - Write Mode

on Page 12

Dual Master (Virtual Peer-to-Peer) - Read Mode (Dual Polling)

on Page 12

Filtering and Data Extraction Functionality (Patent Pending)

on Page 13

1.4.4.1. PLC Master/DeviceMaster UP Slave Mode

PLC Master/DeviceMaster
UP Slave
mode:

Standard Modbus
master to slave device
method of
communication. All
read and write
messages are initiated
by the Modbus master.

Raw/ASCII, Modbus/
RTU slave, and
Modbus/ASCII slave
devices are supported in
this mode.

For raw/ASCII mode, the Receive Transfer mode and Transmit Transfer mode are both set to Slave (In
Modbus/RTU-to-Slaves and Modbus/ASCII-to-Slaves mode, the DeviceMaster UP port only operates in
To-Slave mode.

1.4.4.2. PLC Slave/DeviceMaster UP Master Mode

PLC slave/DeviceMaster UP
master
mode:

The DeviceMaster UP
initiates all read and
write messages.

The DeviceMaster UP
writes received serial
and/or Ethernet device
data directly into PLC
memory with minimal
latency.

The DeviceMaster UP
polls the PLC for transmit data for serial and/or Ethernet devices.

PLC programs can be simplified to eliminate both polling for received data and sending of write messages
to transmit data.

Only raw/ASCII devices are supported in this mode.

The DeviceMaster UP Receive Transfer mode and Transmit Transfer mode are both set to Master.