Testing your new thermostat, Programming user settings – Braeburn 5200 User Manual

Page 4

background image

6

7

NOTE: Test your thermostat prior to programming any user settings. Pressing the

Installer CLEAR button will reset the thermostat to all factory defaults. Pressing

the User RESET button will erase all user settings and return them to their

default values.
1. Place the system switch in the HEAT position.
2. Press the button on the keypad until the set point temperature setting is a
minimum of 3 degrees higher than the current room temperature. The heating
system should start within several seconds. The fan may not turn on

immediately due to the heating system built-in fan delay.
3. Place the system switch in the OFF position. The heating system should stop
within several seconds.
4. Place the system switch in the COOL position.
5. If the compressor has previously been running, then you must wait five

minutes. You can also press the

RESET button to bypass this feature for initial

testing purposes. Pressing the

RESET button will erase any user entries

previously programmed.
6. Press the button on the keypad until the set point temperature is a minimum
of 3 degrees lower than the current room temperature.
7. The cooling system should start within several seconds. Place the system

switch in the

OFF position. The cooling system should stop within 90 seconds

(dependent on the setting of the Residual Cooling Fan Feature).
8. Place the fan switch in the ON position. The system blower should start.
9. Place the fan switch in the AUTO position. The system blower should stop.

Setting Current Time of Day and Day of Week
NOTE:
It is important for you to set the current time of day (note AM/PM

indicator in display), and the current day of week correctly to avoid problems

with program execution.
1. When in normal operating mode, press
the

DAY/TIME keypad button. The LCD

display will be cleared except for the time,
am/pm indicator and the day of the week.
The hour portion of the time will flash.
2. Press the or button to set the
current hour.
3. Press the DAY/TIME button again. The minute portion of the time will flash.
4. Press the or button to set the current minute.
5. Press the DAY/TIME button again. The day of the week indicator will flash.
6. Press the or button to set the current day of the week.
NOTE: The thermostat will return to normal operating mode automatically after

30 seconds if no key is pressed. It will also return to normal operating mode

immediately if the RETURN button is pressed.

cont.

Programming Installer Settings

Testing Your New Thermostat

4

3

WARNING!

Read BEFORE Testing

Testing Your New Thermostat

4

cont.

Programming User Settings

5

3. Selects single stage conventional (11C), 2 stage conventional (22C), single
stage heat pump (11HP), or 2 stage heat pump (22HP). Any change made to
the system type resets Installer Options 4, 5, 6, 9 and 10 to their default

values dependent on system selected.
4. Selects between 1st stage gas or electric heat. This Installer Option is not

available with a heat pump system.
5. Selects between 2nd stage gas or electric heat. This Installer Option is only
available with a 2 stage heat pump system.
6. For heat pump units with an electric auxiliary stage, both the first and second
stages of heating will run when a call for second stage heat is made. For heat
pump units with a fossil fuel auxiliary stage, the first stage will be locked out
one minute after a second stage heat call, and the second stage will only

be used.
7. During the COOL mode of normal operation the fan will stay on for 60 seconds
after the cooling system has satisfied the set point temperature and has

turned off the compressor. This allows the system to provide higher efficiency
during cooling operation.
8. This thermostat includes an automatic compressor protection feature to
avoid potential damage to the cooling system from short cycling. This thermostat
automatically provides a delay after turning off the cooling system output to
protect the compressor. This protection is also present in the heat mode of

operation on single stage heat pump systems to protect the compressor. To
disable this feature, set this option to SSPOF (off).
9. This thermostat provides cold weather compressor protection by locking out
the compressor stage (1st stage) of heating for a period of time after a power
outage greater than 60 minutes. The lockout period is one hour less than the
outage time, up to a maximum of 12 hours. During that period of time, the

auxiliary heat stage will still be available to maintain the set point temperature.
The compressor lockout can be disabled by setting this option to

OFF.

10. Select between turning the AC power interrupt warning off or on. During a

power loss, the thermostat will display an outage warning. The system clock
will continue to run, and all settings will be maintained until the outage period
is over. This Installer Option is only available when thermostat is installed as a
hardwired unit.
11. Selects preferred temperature scale of either ºF or ºC.

• Do not short (or jumper) across terminals on the gas valve or at the heating or
cooling system control board to test the thermostat installation. This could

damage the thermostat and void the warranty.
• Do not select COOL mode of operation if the outside temperature is below 50˚ F
(10˚ C). This could possibly damage the controlled cooling system and may
cause personal injury.
• This thermostat includes an automatic compressor protection feature to avoid
potential damage to the cooling system from short cycling. This thermostat

automatically provides a 5-minute delay after turning off the cooling or heating
system output to protect the compressor. This delay can be disabled in Installer
Option 8 (see Section 3).