Programming installer settings – Braeburn 5200 User Manual
Page 3
4
5
Programming Installer Settings
3
cont.
When the User
RESET button is pressed, the following options will reset to the
factory defaults. All other settings are saved when the
RESET button is pressed.
Function
Status After RESET
Programming
Default setting depending on programming mode
setting (see Section 4). For manual mode:
Heat - 62° F, Cool - 83° F.
Clock
12:00 p.m., Monday
1st Stage Differential
0.5° F (0.25° C)
2nd Stage Differential
2° F (1.0° C)
Filter Check Monitor
0 days-off, Time reset
Keypad Lock Unlocked
Temperature Hold
Permanent and Temporary Hold Cleared,
Reset to Long Hold
Short Cycle Protection Timer
On, Reset
Programming Installer Settings
3
cont.
Setting Thermostat Installer Options
The Installer Options section allows the system and programming parameters
to be set up at installation. The Installer Options mode is menu driven. As the
different options are programmed you may eliminate specific options. For
example, if the system is set to single stage heat pump in Option 3, the selection
for first stage fan control will no longer be available.
To enter the installer settings mode:
Press and hold the
RETURN and buttons at the same time for 3 seconds until
installer option 1 (Programming Mode) is diplayed. Pressing the or buttons will
scroll between choices. To scroll to the next installer option, press the
RETURN
button. To scroll backwards, press the
PROG button. The thermostat will return to
normal operating mode after the last Installer Option mode has been set or by
pressing the
RETURN and PROG buttons at the same time.
NOTE: The thermostat will return to normal operating mode automatically after
30 seconds if no key is pressed.
NOTE: Any changes to Installer Option 3 (System Type) will cause Options 4, 5, 6,
9 and 10 to reset to the default values that are dependent on system selection.
Any changes to Installer Options 1 or 11 will cause all User Options and
Programming to reset to their default values if the User Options were previously
programmed. See Section 5.
Installer Options Factory Default Option
Comment
1 – Programming
pro7
pro7, pro52
Selects the programming mode:
Mode
proNO
7 day, 5-2 day or non-prog.
2 – Enable / Disable
recOF
recON, recOF
Enables or disables early recovery.
ARM
TM
Not available in non-prog. mode.
3 – System Type
11
C
11
C,
22
C,
11
HP
Selects single stage conventional,
22
HP
2 stage conventional, single stage
heat pump or 2 stage heat pump.
4 – First Stage
1
H6
1
H6,
1
HE
Not available with a heat pump
Fan Control
system. Selects between 1st stage
gas or electric heat.
5 – Second Stage
2
HE
2
HE,
2
H6
Only available with a 2nd stage
Fan Control
heat pump system.
6 – Fossil Fuel
au HE
au HE, au H6
Only available with a 2nd stage
Backup Option
heat pump system. Locks out 1st
stage during 2nd stage heat call
for fossil fuel back-up system
(AUHG) With an electric back-up
system (AUHE), both stages will run.
7 – Residual Cooling
fan60
fan00, fan30,
Selects 0, 30, 60 or 90 seconds as
Fan Off Delay
fan60, fan90
the time the fan will stay on after
the cooling system has satisfied the
set point temperature and has
turned off the compressor.
8 – Short Cycle
sspON
sspON, sspOF
Selects SSPON (5 minutes) or
Protection
SSPOF (off) for the compressor
short cycle protection.
9 – Compressor
copOF
copOF, copON
Only available with 2nd stage
Power Outage
heat pump and AC power
Protection
connected. Select between
compressor lock off or
compressor lock on.
10 – AC Power
aciOF
aciOF, aciON
Only available when thermostat
Interrupt Warning
is installed as a hardwired unit.
Select between turning the AC
power interrupt warning off or on.
11 – Temperature
de
6
F
de
6
F, de
6
C
Selects either Fahrenheit
Scale
or Celsius.
Description of Options
1. Selects the programming mode, either full 7 day or 5-2 day
(weekday-weekend) programming or non-programmable.
2. Enables or disables the ARM™ feature. During ARM™, room temperature is
recovered gradually by turning on the heating or cooling before the end of the
set back period. In a multi-stage configuration, room temperature is recovered
gradually by using only the first stage heating or cooling until the last 20
minutes, to minimize the use of the 2nd stage heating or cooling. The set
point temperature is changed to that of the upcoming comfort program
temperature. ARM™ does not operate when the unit is in the temporary or
permanent HOLD mode if the program is temporarily overridden or if
emergency heat is selected for multi-stage heat pumps. If the ARM™ feature
is disabled the thermostat will recover the set point temperature at the
programmed set point time after the setback period ends. (continued on page 6)