Programming installer settings – Braeburn 5200 User Manual

Page 3

background image

4

5

Programming Installer Settings

3

cont.

When the User

RESET button is pressed, the following options will reset to the

factory defaults. All other settings are saved when the

RESET button is pressed.

Function

Status After RESET

Programming

Default setting depending on programming mode

setting (see Section 4). For manual mode:

Heat - 62° F, Cool - 83° F.

Clock

12:00 p.m., Monday

1st Stage Differential

0.5° F (0.25° C)

2nd Stage Differential

2° F (1.0° C)

Filter Check Monitor

0 days-off, Time reset

Keypad Lock Unlocked
Temperature Hold

Permanent and Temporary Hold Cleared,

Reset to Long Hold

Short Cycle Protection Timer

On, Reset

Programming Installer Settings

3

cont.

Setting Thermostat Installer Options
The Installer Options section allows the system and programming parameters
to be set up at installation. The Installer Options mode is menu driven. As the

different options are programmed you may eliminate specific options. For

example, if the system is set to single stage heat pump in Option 3, the selection

for first stage fan control will no longer be available.

To enter the installer settings mode:

Press and hold the

RETURN and buttons at the same time for 3 seconds until

installer option 1 (Programming Mode) is diplayed. Pressing the or buttons will

scroll between choices. To scroll to the next installer option, press the

RETURN

button. To scroll backwards, press the

PROG button. The thermostat will return to

normal operating mode after the last Installer Option mode has been set or by

pressing the

RETURN and PROG buttons at the same time.

NOTE: The thermostat will return to normal operating mode automatically after

30 seconds if no key is pressed.

NOTE: Any changes to Installer Option 3 (System Type) will cause Options 4, 5, 6,

9 and 10 to reset to the default values that are dependent on system selection.

Any changes to Installer Options 1 or 11 will cause all User Options and

Programming to reset to their default values if the User Options were previously

programmed. See Section 5.

Installer Options Factory Default Option

Comment

1 – Programming

pro7

pro7, pro52

Selects the programming mode:

Mode

proNO

7 day, 5-2 day or non-prog.

2 – Enable / Disable

recOF

recON, recOF

Enables or disables early recovery.

ARM

TM

Not available in non-prog. mode.

3 – System Type

11

C

11

C,

22

C,

11

HP

Selects single stage conventional,

22

HP

2 stage conventional, single stage

heat pump or 2 stage heat pump.

4 – First Stage

1

H6

1

H6,

1

HE

Not available with a heat pump

Fan Control

system. Selects between 1st stage

gas or electric heat.

5 – Second Stage

2

HE

2

HE,

2

H6

Only available with a 2nd stage

Fan Control

heat pump system.

6 – Fossil Fuel

au HE

au HE, au H6

Only available with a 2nd stage

Backup Option

heat pump system. Locks out 1st

stage during 2nd stage heat call

for fossil fuel back-up system

(AUHG) With an electric back-up

system (AUHE), both stages will run.

7 – Residual Cooling

fan60

fan00, fan30,

Selects 0, 30, 60 or 90 seconds as

Fan Off Delay

fan60, fan90

the time the fan will stay on after

the cooling system has satisfied the

set point temperature and has

turned off the compressor.

8 – Short Cycle

sspON

sspON, sspOF

Selects SSPON (5 minutes) or

Protection

SSPOF (off) for the compressor

short cycle protection.

9 – Compressor

copOF

copOF, copON

Only available with 2nd stage

Power Outage

heat pump and AC power

Protection

connected. Select between

compressor lock off or

compressor lock on.

10 – AC Power

aciOF

aciOF, aciON

Only available when thermostat

Interrupt Warning

is installed as a hardwired unit.

Select between turning the AC

power interrupt warning off or on.

11 – Temperature

de

6

F

de

6

F, de

6

C

Selects either Fahrenheit

Scale

or Celsius.

Description of Options
1.
Selects the programming mode, either full 7 day or 5-2 day

(weekday-weekend) programming or non-programmable.
2. Enables or disables the ARM™ feature. During ARM™, room temperature is
recovered gradually by turning on the heating or cooling before the end of the
set back period. In a multi-stage configuration, room temperature is recovered
gradually by using only the first stage heating or cooling until the last 20

minutes, to minimize the use of the 2nd stage heating or cooling. The set

point temperature is changed to that of the upcoming comfort program

temperature. ARM™ does not operate when the unit is in the temporary or

permanent HOLD mode if the program is temporarily overridden or if

emergency heat is selected for multi-stage heat pumps. If the ARM™ feature
is disabled the thermostat will recover the set point temperature at the

programmed set point time after the setback period ends. (continued on page 6)