beautypg.com

2 electrical installation, Am series cascade sequencer – AERCO AM Series Boiler Cascade Sequencer Controller User Manual

Page 6

background image

AM Series Cascade Sequencer

INSTALLATION AND OPERATION MANUAL

1.2 Electrical Installation

The electrical installation must be done as shown in Figure 1-2.
Installer must install all wires represented by dashed lines. The “Cascade general sensor” is

present inside each heater’s accessory box. This sensor must be electrically wired to terminals

24 and 25 of the Managing heater # 1 and placed into the low loss header of the cascade (see

Figure 1-1).
The "daisy chain" wiring used to connect boilers should be shielded type and has a

maximum length of 300 ft. Unshielded wire is acceptable but not recommended, and the

maximum length is only 60 ft.
Depending on the control method of your system, additional wiring may be required. For

outdoor reset using the included outdoor temperature sensor, connect the outdoor

temperature sensor to terminals 14 & 15 of the managing boiler. For remote setpoint (0-10V)

control, connect the 0-10V signal wires to terminals 22 & 23 of the master boiler. For Modbus

control of the operating setpoint connect to terminals 18, 19, and 20. For further information

on Modbus, see GF-146-MB.
If there is a water heater tank present in the system, whether direct or indirect, the tank

sensor should be placed in the bottom 1/3 of the tank and wired into terminals 12 & 13 of

the managing heater. This sensor is included in the spare parts kit shipped with each unit,

and is the same probe as the cascade header temperature sensor.
For further information on all of these control modes, consult the AM Series Boiler and

Water Heater User Manual (GF-146).

Page 6 of 26

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0101_0A

PRI - 11/25/14

Ph.: 800-526-0288

GF-146-CS