AM Series Cascade Sequencer

INSTALLATION AND OPERATION MANUAL

2.5 Sub-menu Parameter Range and Default settings

Below is a list of the menu parameters with range and default settings. There is a table in the

previous section that provides a description of each parameter.

AM Series Cascade Sequencer Sub-Menu Parameter List

Parameter

Units

Range

Factory

Settings

Boiler Settings

Water Heater

Settings

Custom

Value

Boiler address

/

0 …..16

0

0 - Stand Alone heater

1 – Managing Heater

2 – 1st Dependent Heater

3 – 2nd Dependent Heater

4 – 3rd……etc

0 - Stand Alone heater

1 – Managing Heater

2 – 1st Dependent Heater

3 – 2nd Dependent Heater

4 – 3rd……etc

Cascade setpoint

°F

68..194

140

140

140

DHW ON..OFF

/

ON..OFF

OFF

ON (only if you want to drive

an indirect water heater)

OFF

Start delay time

sec

0..1200

180

180

15

Stop delay time

sec

0..1200

180

180

15

Start boiler diff

°F

14..36

14

14

14

Stop boiler diff

°F

14..59

14

14

14

Stop all boiler diff

°F

14..59

24

24

24

Max offset up

°F

14..50

17

17

14

Max offset down

°F

14..50

37

37

14

Rotation interval

Days

1..10

5

5

5

P Value

/

0..255

20

20

20

I Value

/

0..255

80

80

80

D Value

/

0..255

0

0

0

Slew rate

/

1..255

5

5

5

System correction

°F

14..32

22.1

22.1

22.1

Mod delay factor

min

0..60

4

4

0

OMM-0101_0A