5 sub-menu parameter range and default settings, 4 submenu parameter list, Am series cascade sequencer – AERCO AM Series Boiler Cascade Sequencer Controller User Manual
Page 23

AM Series Cascade Sequencer
INSTALLATION AND OPERATION MANUAL
2.5 Sub-menu Parameter Range and Default settings
Below is a list of the menu parameters with range and default settings. There is a table in the
previous section that provides a description of each parameter.
AM Series Cascade Sequencer Sub-Menu Parameter List
Parameter
Units
Range
Factory
Settings
Boiler Settings
Water Heater
Settings
Custom
Value
Boiler address
/
0 …..16
0
0 - Stand Alone heater
1 – Managing Heater
2 – 1st Dependent Heater
3 – 2nd Dependent Heater
4 – 3rd……etc
0 - Stand Alone heater
1 – Managing Heater
2 – 1st Dependent Heater
3 – 2nd Dependent Heater
4 – 3rd……etc
Cascade setpoint
°F
68..194
140
140
140
DHW ON..OFF
/
ON..OFF
OFF
ON (only if you want to drive
an indirect water heater)
OFF
Start delay time
sec
0..1200
180
180
15
Stop delay time
sec
0..1200
180
180
15
Start boiler diff
°F
14..36
14
14
14
Stop boiler diff
°F
14..59
14
14
14
Stop all boiler diff
°F
14..59
24
24
24
Max offset up
°F
14..50
17
17
14
Max offset down
°F
14..50
37
37
14
Rotation interval
Days
1..10
5
5
5
P Value
/
0..255
20
20
20
I Value
/
0..255
80
80
80
D Value
/
0..255
0
0
0
Slew rate
/
1..255
5
5
5
System correction
°F
14..32
22.1
22.1
22.1
Mod delay factor
min
0..60
4
4
0
OMM-0101_0A