beautypg.com

6 setting for use with boilers or water heaters, Am series cascade sequencer – AERCO AM Series Boiler Cascade Sequencer Controller User Manual

Page 17

background image

AM Series Cascade Sequencer

INSTALLATION AND OPERATION MANUAL

Setting the Logic Address for Each Heater - Continued

11. Repeat steps a) through g) in Step 5 setting the logic address to 2.
12. Turn the power OFF to the Dependent heater #2.
13. On the communications board at top of unit, set the S4 Switch (see Figure 1-13) to the OFF

position.

14. Disconnect the two wires from terminals 16 and 17 of the Dependent heater #2.
15. Repeat steps 1 to 13 on each dependent heater and set the Address sequentially for each

one (2, 3, 4, 5, etc.).

16. After all dependent heaters have had the logic address set, wire the Cascade Sequencer to

terminals 16 and 17 of the Managing heater #1. The Cascade Sequencer is now set up for

cascade operation. Ensure all switch settings match Figure 1-18.

1.6 Setting for Use with Boilers or Water Heaters

The Cascade Sequencer is set at the factory for boiler applications, but not for water heater

applications. When your system is in place, and you wish to control water heaters, you must

ensure all parameters of the Sub Menu are set as shown in the list in Section 2.1. Select the

settings in the column for boilers if you are using boilers, or select the settings in the column for

water heaters if you are using water heaters.

1.7 Dependent Heater Preparation – Setting Parameter 2003

Parameter 2003 is factory set to 0. However, this parameter should be checked for all

dependent heaters to ensure parameter 2003 is set to 0.
Follow the instructions in Section 1.71 (next page) to access the Installer Menu on the AM

Series boiler or water heater controller to confirm or change parameter 2003 to zero for all

dependent heaters. If you need more information concerning AM Series controller operation,

consult the AERCO AM Series user manual (GF-146).













OMM-0101_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 17 of 26

GF-146-CS

Ph.: 800-526-0288

PRI - 11/25/14