6 setting for use with boilers or water heaters, Am series cascade sequencer – AERCO AM Series Boiler Cascade Sequencer Controller User Manual
Page 17

AM Series Cascade Sequencer
INSTALLATION AND OPERATION MANUAL
Setting the Logic Address for Each Heater - Continued
11. Repeat steps a) through g) in Step 5 setting the logic address to 2.
12. Turn the power OFF to the Dependent heater #2.
13. On the communications board at top of unit, set the S4 Switch (see Figure 1-13) to the OFF
position.
14. Disconnect the two wires from terminals 16 and 17 of the Dependent heater #2.
15. Repeat steps 1 to 13 on each dependent heater and set the Address sequentially for each
one (2, 3, 4, 5, etc.).
16. After all dependent heaters have had the logic address set, wire the Cascade Sequencer to
terminals 16 and 17 of the Managing heater #1. The Cascade Sequencer is now set up for
cascade operation. Ensure all switch settings match Figure 1-18.
1.6 Setting for Use with Boilers or Water Heaters
The Cascade Sequencer is set at the factory for boiler applications, but not for water heater
applications. When your system is in place, and you wish to control water heaters, you must
ensure all parameters of the Sub Menu are set as shown in the list in Section 2.1. Select the
settings in the column for boilers if you are using boilers, or select the settings in the column for
water heaters if you are using water heaters.
1.7 Dependent Heater Preparation – Setting Parameter 2003
Parameter 2003 is factory set to 0. However, this parameter should be checked for all
dependent heaters to ensure parameter 2003 is set to 0.
Follow the instructions in Section 1.71 (next page) to access the Installer Menu on the AM
Series boiler or water heater controller to confirm or change parameter 2003 to zero for all
dependent heaters. If you need more information concerning AM Series controller operation,
consult the AERCO AM Series user manual (GF-146).
OMM-0101_0A
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 17 of 26
GF-146-CS
Ph.: 800-526-0288
PRI - 11/25/14