1 am series controller - installer menu navigation, Am series cascade sequencer – AERCO AM Series Boiler Cascade Sequencer Controller User Manual
Page 18

AM Series Cascade Sequencer
INSTALLATION AND OPERATION MANUAL
1.7.1 AM Series Controller - Installer Menu Navigation
This menu of parameters is available to qualified technicians for the purpose of analyzing the
function of, and making adjustments to, the unit.
Parameters for “Burner 1” are applicable for that burner only.
To enter and make changes in the Installer Menu, perform the following steps:
AM Series Controller - Installer Menu Navigation and Adjustment
1. To enter the Installer Menu, press and simultaneously hold down both the
RESET
and
buttons or 5 seconds until the icon is displayed.
, then release the buttons.
After entering the Installer Menu, the 2000 series of parameters are available for display and
editing.
2. To scroll through the list of parameters, press buttons
and
.
3. Once parameter 2003 is displayed, it can be selected for editing by pressing the
RESET
button once (the displayed value will start blinking) and then using the
and
buttons to change the value, up or down. For dependent eaters, select 0.
4. To confirm the new value, press and release the
RESET
button.
5. To exit the Installer Menu, press and hold RESET button for more than 5 seconds until the
icon is no longer shown in the display.
NOTE
This instruction is only for setting parameter 2003. For information
about other parameters in the Installer Menu, refer to the AM
Series user manual (GF-146).