Appendix j, Table j-1. bms commands – (continued) – AERCO BMS 168 User Manual

Page 81

background image

J

-

5

Appendix J

(cont.)

__________________________


Table J-1. BMS COMMANDS – (Continued)


No.


COMMAND


ENTRY RANGE

FACTORY

DEFAULT

45 (Day

1)

Thru Offset ON Time – Minutes (Day 1-7)

00 to 59

All Set to Zero

51 (Day

7)

52 (Day

1)

Thru

Offset ON Time – Hours (Day 1-7)

00 to 23

All Set To Zero

58 (Day

7)

59

Offset Enable

0 = Disabled
1 = Enabled

0 = Disabled

60

Header Offset (°F)

0 to 5

0

61

System Start Relay Contact Operation
With Interlocks

0 = No Action
1 = Either Intlk Opens
Start Relay
2 = Intlk 1 Opens Start
Relay
3 = Intlk 2 Opens Start
Relay

0 = No Action

70 (Day

1)

Thru Offset OFF Time – Minutes (Day 1-7)

00 to 59

All Set To Zero

76 (Day

7)

77 (Day

1)

Thru Offset OFF Time – Hours (Day 1-7)

0 to 23

All Set To Zero

83 (Day

7)

84 (Reserved)

85

Indoor Air Input

0 or 1
0 = 4 - 20 mA
1 = Thermistor

1 = Thermistor

Command Nos. 86 and Up Apply Only to BMS Units Equipped With Modbus Capability

86

Remote Signal

0 or 1
0 = 4 - 20 mA
1 = Modbus

0 = 4 - 20 mA