Table J-1. BMS COMMANDS


No.


COMMAND


ENTRY RANGE

FACTORY

DEFAULT

00

Header Temperature (°F)

40 to 220

Read Only

01

Outside Air Temperature (°F)

-60 to 80

Read Only

02

Indoor Air Temperature (°F)

40 to 160

Read Only

03

Fire Rate (%)

0 to 100

Read Only

04

Header Set Temperature (°F)

40 to 220

Read Only

05

System Outside Air Start Temperature
(°F)

32 to 120

70

06

System Start Mode

0 = Temp Only
1 = Temp and Load

0 = Temp Only

07

Manual Header Set Temperature (°F)

40 to 220

160

08

Reference Temperature (°F)

40 to 220

70°F

09

Indoor Prop Band

0.0 to 20.0

(0.1 increments)

0.0

10

Setpoint Temperature(°F)

40 to 220

160

11

Reset Ratio

0.3 to 3.0

(0.1 increments)

1.2

12

Maximum Header Temperature (°F)

40 to 220

220

13

Minimum Header Temperature (°F)

40 to 220

40

14

Boiler Start Percent

25 to 100

45

15

Boiler Stop Percent

10 to 45

18

16

Integral Gain (Rep./Min)

0.00 to 9.99

(0.01 increments)

0.15

17

Header Set Mode

0 = Constant Settemp
1 = Indr/Outdr Reset
2 = Remote Settemp

1 = Indr/Outdr Reset

18

Derivative Gain

-2.00 to 2.00

(0.01 increments)

0.15

19

Header Bandwidth (°F)

5 to 100

70

20

Aux Relay Off Level (%)

0 to 99

45