Appendix j, Table j-1. bms commands – AERCO BMS 168 User Manual
Page 79

Appendix J
(cont.)
__________________________
Table J-1. BMS COMMANDS
No.
COMMAND
ENTRY RANGE
FACTORY
DEFAULT
00
Header Temperature (°F)
40 to 220
Read Only
01
Outside Air Temperature (°F)
-60 to 80
Read Only
02
Indoor Air Temperature (°F)
40 to 160
Read Only
03
Fire Rate (%)
0 to 100
Read Only
04
Header Set Temperature (°F)
40 to 220
Read Only
05
System Outside Air Start Temperature
(°F)
32 to 120
70
06
System Start Mode
0 = Temp Only
1 = Temp and Load
0 = Temp Only
07
Manual Header Set Temperature (°F)
40 to 220
160
08
Reference Temperature (°F)
40 to 220
70°F
09
Indoor Prop Band
0.0 to 20.0
(0.1 increments)
0.0
10
Setpoint Temperature(°F)
40 to 220
160
11
Reset Ratio
0.3 to 3.0
(0.1 increments)
1.2
12
Maximum Header Temperature (°F)
40 to 220
220
13
Minimum Header Temperature (°F)
40 to 220
40
14
Boiler Start Percent
25 to 100
45
15
Boiler Stop Percent
10 to 45
18
16
Integral Gain (Rep./Min)
0.00 to 9.99
(0.01 increments)
0.15
17
Header Set Mode
0 = Constant Settemp
1 = Indr/Outdr Reset
2 = Remote Settemp
1 = Indr/Outdr Reset
18
Derivative Gain
-2.00 to 2.00
(0.01 increments)
0.15
19
Header Bandwidth (°F)
5 to 100
70
20
Aux Relay Off Level (%)
0 to 99
45
J
-
3