beautypg.com

Installation – Carrier 38AU User Manual

Page 9

background image

9

Matching 38AU Model To Evaporator Coil –

The Model 38AUZ is a single-circuit unit design, requiring one

set of refrigeration piping. This model can be connected to an

evaporator coil with one circuit or with two circuits (by mani-

folding the evaporator connections into a single piping system).
The Model 38AUD is a dual-circuit unit design that requires

two sets of refrigeration piping between the outdoor unit and

the evaporator coil (or coils). This model can only be connect-

ed to an evaporator coil that has two refrigeration circuits (or to

two separate evaporator coils). The Model 38AUD CANNOT

be connected to a single-circuit evaporator coil. The Model

38AUD CANNOT be field-converted to a single-circuit de-

sign.
Before unpacking this new 38AU model, compare the evapora-

tor coil design to the 38AU model.

Table 3 — Evaporator Coil Connections

INSTALLATION

Jobsite Survey

Complete the following checks before installation.

1. Consult local building codes or the U.S. A. National Elec-

trical Code (Ref: ANSI/NFPA 70 [American National

Standards Institute/National Fire Protection Association],

latest version) for special installation requirements.

2. Determine unit location (from project plans) or select unit

location.

3. Check for possible overhead obstructions which may in-

terfere with unit lifting or rigging.

Step 1 — Plan for Unit Location

Select a location for the unit and its support system (pad, rails

or other) that provides for the minimum clearances required for

safety. This includes minimum working space, clearances be-

tween live electrical components and nearest barriers (ground-

ed or ungrounded), clearances for unit performance and service

access below, around and above unit as specified in unit draw-

ings. See Fig. 4.
NOTE: Local codes may require different clearances than

specified in Fig. 4. It is the responsibility of installers to be

knowledgeable in local codes and to modify the recom-

mended clearances to satisfy local codes.
NOTE: Consider also the effect of adjacent units on airflow

performance and control box safety clearance.
Do not install the outdoor unit in an area where fresh air supply

to the outdoor coil may be restricted or when recirculation from

the condenser fan discharge is possible. Do not locate the unit

in a well or next to high walls.
Evaluate the path and required line length for interconnecting

refrigeration piping, including suction riser requirements (out-

door unit above indoor unit), liquid line lift (outdoor unit below

indoor unit) and hot gas bypass line. Relocate sections to mini-

mize the length of interconnecting tubing.

Although unit is weatherproof, avoid locations that permit

water from higher level runoff and overhangs to fall onto the

unit.

Fig. 4 — Service Clearance Dimensional Drawing

Step 2 — Complete Pre-Installation Checks

CHECK UNIT ELECTRICAL CHARACTERISTIC —

Confirm before installation of unit that voltage, amperage and

circuit protection requirements listed on unit data plate agree

with power supply provided.
— UNCRATE UNIT — Remove unit packaging except for

the top skid assembly, which should be left in place until after

the unit is rigged into its final location.
INSPECT SHIPMENT — File a claim with shipping compa-

ny if the shipment is damaged or incomplete.

CONSIDER SYSTEM REQUIREMENTS

• Consult local building codes and National Electrical

Code (NEC, U.S.A.) for special installation requirements.

• Allow sufficient space for airflow clearance, wiring,

refrigerant piping, and servicing unit. See Fig.1 for unit

dimensions and weight distribution data.

• Locate the unit so that the outdoor coil (condenser) air-

flow is unrestricted on all sides and above.

• The unit may be mounted on a level pad directly on the

base channels or mounted on raised pads at support

points. See Tables 1A through 2B for unit operating

weights. See Fig. 1 for weight distribution based on rec-

ommended support points.

NOTE: If vibration isolators are required for a particular

installation, use the data in Fig. 1 to make the proper

selection.

Step 3 — Prepare Unit Mounting Support
Slab Mount —

Provide a level concrete slab that extends a minimum of 150

mm (6 in.) beyond unit cabinet. Install a gravel apron in front

of condenser coil air inlet to prevent grass and foliage from

obstructing airflow.

Step 4 — Rig and Mount the Unit

RIGGING — These units are designed for overhead rigging.

Refer to the rigging label for preferred rigging method. Spread-

er bars are not required if top crating is left on the unit. All pan-

els must be in place when rigging. As further protection for coil

Evaporator Coil has Connect to Model Notes

Single Circuit

38AUZ ONLY

Two Circuits

38AUZ

Manifold evaporator

circuits into single

piping system

Or

38AUD

Use two separate

piping systems

DO NOT BURY REFRIGERATION LINES.

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment

damage.
All panels must be in place when rigging. Unit is not

designed for handling by fork truck.

REAR:
Min 457 mm (18”)
requried for service

Note: Observe requirements for 914 mm (39”) operating clearance

on either Left or Rear coil opening.

RIGHT:
Min 457 mm (18”)
requried for service

LEFT:
Min 457 mm (18”)
requried for service

FRONT:
1067 mm (42”)