CL-1

III. START UP

START-UP CHECKLIST

I. PRELIMINARY INFORMATION

OUTDOOR: MODEL NO.

SERIAL NO.

INDOOR: AIR HANDLER MANUFACTURER

MODEL NO.

SERIAL NO.

ADDITIONAL ACCESSORIES

II. PRE-START-UP

OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE?

(Y/N)

IF SO, WHERE:

WILL THIS DAMAGE PREVENT UNIT START-UP?

(Y/N)

CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?

(Y/N)

HAS THE GROUND WIRE BEEN CONNECTED?

(Y/N)

HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?

(Y/N)

ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?

(Y/N)

CONTROLS
ARE THERMOSTAT AND INDOOR FAN CONTROL WIRING CONNECTIONS MADE AND CHECKED?

(Y/N)

ARE ALL WIRING TERMINALS (including main power supply) TIGHT?

(Y/N)

HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS?

(Y/N)

INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE?

(Y/N)

ARE PROPER AIR FILTERS IN PLACE?

(Y/N)

HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT?

(Y/N)

DO THE FAN BELTS HAVE PROPER TENSION?

(Y/N)

HAS CORRECT FAN ROTATION BEEN CONFIRMED?

(Y/N)

PIPING
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR COILS AS REQUIRED?

(Y/N)

HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, OUTDOOR AND INDOOR COILS,

TXVs (Thermostatic Expansion Valves), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS

WITH A LEAK DETECTOR?

(Y/N)

LOCATE, REPAIR, AND REPORT ANY LEAKS.
HAVE LIQUID LINE SERVICE VALVES BEEN OPENED?

(Y/N)

HAVE SUCTION SERVICE VALVES BEEN OPENED?

(Y/N)

CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS:

AB

V

AC

V

BC

V

(AB + AC + BC)/3 = AVERAGE VOLTAGE =

V

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =

V

VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!

CALL LOCAL POWER COMPANY FOR ASSISTANCE.