beautypg.com

Carrier 38AU User Manual

Page 12

background image

12

INSULATE SUCTION LINES — Apply closed-cell tubular

insulation to all suction lines between evaporator coil

connection and 38AU unit’s suction service valve.
Hot Gas Bypass – Hot gas bypass, if used, should be

introduced before the evaporator. (A bypass route that also

bypasses the evaporator circuit may lead to oil trapping in the

evaporator circuit during low load conditions and then to oil

slugging as evaporator load increases.) Model 38AU units do

not include a hot gas stub connection; a tee must be field-

supplied and installed in the compressor discharge line. Run a

½-in OD line between outdoor unit and evaporator coil inlet.

Install an Auxiliary Side Connector at the evaporator between

TXV and distributor (follow instructions for the side connector

part). Insulate the hot gas line.
38AUD: Generally only one hot gas bypass system will be

applied on a two-circuit unit. Connect the hot gas bypass

system to Circuit A (first-on/last-off, connected to the

evaporator coil’s bottom circuit).
38AUD PIPING CONNECTIONS – The 38AUD’s two

circuits are designated Circuit A and Circuit B. Circuit A is

controlled by the thermostat’s Y1 (or TC1) contact and will be

the first circuit on and last circuit off. Circuit B is controlled by

the thermostat’s Y2 (or TC2) contact and this circuit is always

the “lag” circuit.
See Fig. 5 for location of the Circuit A and Circuit B service

valves and field piping connections. Circuit A is on the right-

hand side of the service valve compartment; Circuit B is on the

left.

Fig 5 - 38AUD Service Valve Locations

When a single piece evaporator coil with two separate circuits

is connected to a 38AUD, the lower coil circuit should be

connected to the 38AUD’s Circuit A so that the evaporator’s

lower coil segment is first-on/last-off (to avoid re-evaporation

of condensate on dry lower coil segments).
Plan the Circuit A and Circuit B tubing segments carefully,

mark each segment and check constantly as piping systems are

assembled to avoid piping errors.
38AUD unit cannot be field-piped as a single-circuit/tandem

system.
Connecting 40RU to 38AUD – The 40RU fan coil in sizes 12,

14 and 16 is a face-split coil design that also has its circuits

designated as A and B. See Fig. 6. Note that the lower coil

segment changes as the arrangement of the 40RU changes. In a

vertical arrangement, the 40RU’s lower coil segment is

segment B; this segment should be connected to the 38AUD’s

Circuit A. In a horizontal arrangement, the 40RU’s lower

segment is now segment A; this segment should be connected

to the 38AUD’s Circuit A.

Fig. 6 — Typical Evaporator Coil Connections (40RU)

Note that refrigerant suction piping should be insulated.
INSTALL FILTER DRIER(S) AND MOISTURE

INDICATOR(S) — Every unit MUST have a filter drier in the

liquid line. 38AUD models require two filter driers (one in

each liquid line). Locate the filter drier(s) at the indoor unit,

close to the evaporator coil’s thermal expansion valve (TXV)

inlets.
38AU units include one (38AUZ) or two (38AUD) Puron-duty

filter drier(s), shipped in cartons attached to the unit basepan.

Remove the filter drier(s) and prepare to install in the liquid

line(s) at the evaporator coil. Do not remove connection fitting

plugs until ready to connect and braze the filter drier into the

liquid line position.

Table 8 — Puron-duty Filter Drier(s)

Installation of liquid line moisture indicating sightglass in each

circuit is recommended. Locate the sightglass(es) between the

outlet of the filter drier and the TXV inlet.

Circuit A

Connections

Circuit B

Connections

40RU

Arrangement

Cooling

Stage

40RU Coil

Segment

Connect to

38AUD

Vertical

Y1

Y2

B

A

Circuit A

Circuit B

Horizontal

Y1

Y2

A

B

Circuit A

Circuit B

Model-Size

Qty

Liquid

Line OD

Desiccant

Volume

Part

Number Ref

38AUZ*07

1

3

/

8

-in

8 cu. in.

KH43LG091

38AUZ*08

1

1

/

2

-in

16 cu. in.

KH43LG085

38AUD*12

2

3

/

8

-in

8 cu. in.

KH43LG091

38AUD*14

2

1

/

2

-in

16 cu. in.

KH43LG085

FIRST ON/LAST OFF = B

VERTICAL INSTALLATION

FIRST ON/LAST OFF = A

HORIZONTAL INSTALLATION