beautypg.com

Advanced scroll temperature protection (astp), Start unit, Adjust refrigerant charge – Carrier 38AU User Manual

Page 20: Final checks

background image

20

Advanced Scroll Temperature Protection (ASTP)

A label located above the terminal box identifies Copeland

Scroll compressor models that contain this technology. See Fig.

17. Advanced Scroll Temperature Protection (ASTP) is a form

of internal discharge temperature protection, that unloads the

scroll compressor when the internal temperature reaches ap-

proximately 300°F. At this temperature, an internal bi-metal

disk valve opens and causes the scroll elements to separate,

which stops compression. Suction and discharge pressures bal-

ance while the motor continues to run. The longer the compres-

sor runs unloaded, the longer it must cool before the bi-metal

disk resets. See Fig. 18.

Fig. 17 — Advanced Scroll Temperature

Protection Label

Fig. 18 — Recommended Minimum Cool-Down Time

After Compressor is Stopped

To manually reset ASTP, the compressor should be stopped

and allowed to cool. If the compressor is not stopped, the motor

will run until the motor protector trips, which occurs up to

90 minutes later. Advanced Scroll Temperature Protection will

reset automatically before the motor protector resets, which

may take up to 2 hours.

Start Unit

Set the space thermostat to a set point above space temperature

so that there is no demand for cooling. Close the 38 AU discon-

nect switch. Only the crankcase heater will be energized.
Reset the space thermostat below space temperature so that a

call for cooling is ensured.

Adjust Refrigerant Charge

The unit must be charged in Cooling mode only. Refer to Cool-

ing Charging Charts, Fig. 19 through Fig. 22. Vary refrigerant

until the conditions of the chart are met. Note that the charging

charts are different from the type normally used. The charts are

based on charging the units to the correct subcooling for the

various operating conditions. Accurate pressure gage and tem-

perature sensing device are required. Connect the pressure

gage to the service port on the liquid line service valve. Mount

the temperature sensing device on the liquid line close to the

liquid line service valve, and insulate it so that outdoor ambient

temperature does not affect the reading. Indoor airflow must be

within the unit’s normal operating range. Operate the unit for a

minimum of 15 minutes. Ensure that pressure and temperature

readings have stabilized. Plot the liquid pressure and tempera-

ture on chart and add or reduce the charge to meet the curve.

Adjust the charge to conform with the charging chart, using the

liquid pressure and temperature to read the chart.

FINAL CHECKS

Ensure that all safety controls are operating, control panel

covers are on, and the service panels are in place.

0

10

20

30

40

50

60

70

80

90

100

110

120

0

10

20

30

40

50

60

70

80

90

Compressor Unloaded Run Time (Minutes)

R

e

c

o

m

m

e

nde

d C

ool

ing

Ti

m

e

(Mi

nu

tes

)

*Times are approximate.
NOTE: Various factors, including high humidity, high ambient tem-

perature, and the presence of a sound blanket will increase cool-

down times.

Never charge liquid into the low-pressure side of system.

Do not overcharge. During charging or removal of refriger-

ant, be sure indoor-fan system is operating. Ensure both

outdoor fan motors are running; bypass any Motormaster

or mild-ambient control function.