beautypg.com

Carrier 38AU User Manual

Page 18

background image

18

External Devices – The 38AU control transformers provide 24-

v NEC Class 2 power sources to energize external control de-

vices. These devices will include the indoor fan motor contac-

tor (or control relay). These devices may also include liquid

line solenoid valve (two on 38AUD model), economizer con-

trol relay, supplemental electric heater contactors or control re-

lays and other devices selected by system designer.
Control transformer TRAN1 provides control power through

terminal R to C on the CTB’s field connection terminal strip for

supply fan motor interlock. This source may also be used to en-

ergize economizer control relay and electric heater contactors

or relays. Maximum available power is 20 va. Check concur-

rent loadings by external control devices. If the maximum con-

current loading exceeds 20 va, purchase and install the accesso-

ry Transformer-Relay package (available for 208/230 and

460-v units).
Control transformer TRAN3 provides control power through

terminals A1 (9) and A2 (10) to C for liquid line solenoids.

Maximum available power is 40 va. These outputs are

switched ON/OFF by the Solenoid Valve Relays.

Table 11 — Electrical Data — 38AUZ*07-08 60 Hz Units

Table 12 — Electrical Data — 38AUD*12-14 60 Hz Units

LEGEND AND NOTES FOR TABLES 11 & 12

UNIT

SIZE

38AU

NOMINAL

VOLTAGE

VOLTAGE

RANGE

COMPRESSOR

OUTDOOR

FAN MOTORS (ea)

WITHOUT POWERD

CONVENIENCE

OUTLET

WITH POWERD

CONVENIENCE

OUTLET

V-Ph-Hz

MIN

MAX

RLA

LRA

WATTS

FLA

QTY

MCA

MOCP

MCA

MOCP

Z*07

400-3-50

380

420

9.7

64

270

0.7

2

13.5

20

15.9

25

Z*08

400-3-50

380

420

12.2

101

270

0.7

2

16.7

25

19.0

30

UNIT

SIZE

38AU

NOMINAL

VOLTAGE

VOLTAGE

RANGE

COMPRESSOR

1

COMPRESSOR

2

OUTDOOR

FAN MOTORS (ea)

WITHOUT POWERD

CONVENIENCE

OUTLET

WITH POWERD

CONVENIENCE

OUTLET

V-Ph-Hz

MIN

MAX

RLA

LRA

RLA

LRA

WATTS

FLA

QTY

MCA

MOCP

MCA

MOCP

D*12

208/230-3-60

380

420

7.8

51.5

7.8

51.5

270

0.7

2

19.0

25

21.3

30

D*14

208/230-3-60

380

420

10.6

74

10.6

74

270

0.7

2

25.3

30

27.6

30

FLA

Full Load Amps

LRA

Locked Rotor Amps

MCA —

Minimum Circuit Amps

MOCP —

Maximum Overcurrent

Protection

NEC

National Electrical Code

RLA

Rated Load Amps

Units are suitable for use on electrical systems where voltage supplied to

the unit terminals is not below or above the listed limits.

NOTES:

1. The MCA and MOCP values are calculated in accordance with the NEC,

Article 440.

2. Motor RLA and LRA values are established in accordance with

Underwriters’ Laboratories (UL), Standard 1995.

3. The 575-v units are UL, Canada-listed only.

4. Convenience outlet is available as a factory-installed option and is 115-v,

1 ph, 60 Hz.

5. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is

greater than 2%. Use the following formula to determine the percentage

of voltage imbalance.

Example: Supply voltage is 230-3-60

AB = 224 v
BC = 231 v
AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

3

3

=

227

Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage