beautypg.com

Carrier 38AU User Manual

Page 5

background image

5

Table 1B — Physical Data — 38AUZ*07-08 Units — 50 Hz SI

UNIT SIZE 38AU

Z*07

Z*08

NOMINAL CAPACITY (kW)

21.1

26.4

OPERATING WEIGHT (kg)

Aluminum-Fin Coils

149

160

REFRIGERANT TYPE

R-410A

Operating Charge, Typical (kg)

4.1

5.6

Shipping Charge (kg)

2.0

2.2

COMPRESSOR

Qty...Type

1...Scroll

OUTDOOR FANS

Qty...r/s

2...18

Motor Hp NEMA

1

/

4

Diameter (mm)

560

Nominal Airflow (L/s)

2832

Watts (Total)

610

OUTDOOR COIL (Qty)

1...NOVATION

Face Area (sq m total)

1.6

1.9

Rows/Fins per Meter (Fins/m)

1...670

1...670

CONTROLS

Pressurestat Settings (kPa)

High Cutout

4347 ± 70

Cut-in

3482 ±138

Low Cutout

372 ± 21

Cut-in

807 ± 34

PIPING CONNECTIONS (in. ODS)

Qty...Suction

1...1

1

/

8

1...1

1

/

8

Qty...Liquid

1...

3

/

8

1...

1

/

2

LEGEND

NEMA — National Electrical Manufacturers Association

ODS — Outside Diameter Sweat (socket)

‡ Unit is factory-supplied with partial charge only.

† Typical operating charge with 7.62 m of interconnecting piping.