Pilz PSEN op Advanced Programming Adapter User Manual
Operating manual

PSEN op Advanced Programming Adapter
Ethernet Adapter for PSEN op Advanced series
OPERATING MANUAL
1003071-EN-01
SAVE CONFIGURATION
The Adapter can read out the configuration of a Type 4 light curtain of the
PSEN op Advanced series. It can be used both as a backup in case an
exchange of damaged light curtains is required, and for transferring a configuration
to other light curtains used in the same way in the application.
Step 1: Backup of the configuration
Connect the adapter to the light curtain that is used as a source (see section
"Connection").
Press the button
until the symbol
is shown on the display. The backup
procedure is completed when the DL-LED lo longer flashes (see Fig. 1).
DL Button
Yellow DL led
3s < t < 1min
3s
7-Seg Display
DL
Fig. 1 Download of a configuration
Step 2: Reading the configuration
Connect the adapter to the light curtain to which the configuration is to be
transferred (see section "Connection").
Important: The existing configuration in the programming adapter can only be
copied into light curtains with the same hardware.
Press the button
until the symbol
is shown on the display. The process
of writing is completed when the UL-LED no longer flashes (Fig. 2).
Yellow UL led
3s < t < 1min
7-Seg Display
3s
UL
Fig. 2 Reading the configuration
After a configuration has been successfully transferred from the adapter to
the light curtain, a configuration report is saved. A maximum of 10 transfer
processes can be performed. When this number is achieved, the user has to
download the reports using the PSENopt Configurator software.
Step 3: Downloading the reports and checking the light
curtain configuration
Connect the adapter to the Ethernet network and the supply (see section
"Stand-alone connection").
Load all the reports saved in the adapter via PSENopt Configurator.
The serial number and the corresponding configuration parameters are saved in a
configuration report of a certain light curtain.
Before starting normal plant operation, it must be checked
whether the configured light curtains work to the purpose
for which they are intended.
Deleting the configuration reports
Before deleting, ensure that the report has been saved. Press the button (>
3s)
until the symbol
is shown on the display. Then all the reports in
the adapter are deleted.
OFFLINE CONFIGURATION
Via PSENopt Configurator you can prepare a light curtain configuration and
transfer it to the PSEN op Advanced Programming Adapter. This allows offline
configurations to be created which can later be copied to the corresponding light
curtains.
Step 1: Create configuration
Connect the supply voltage and the Ethernet connection correspondingly. (see
section "Stand-alone connection"). In
PSENopt Configurator,
select
"Configuration of the safety light curtain" to start the offline configuration.
Select the corresponding light curtains from the catalogue and drag it to the middle
(max. 3 Types can be cascaded). The select the corresponding programming
adapter from the network and continue setting the parameters with "Continue".
Then use "Programming" to save the corresponding configuration into the
programming adapter PSEN op Advanced Programming Adapter.
The adapter now includes the configuration that can be transferred to several light
curtains.
Important: Select the correct article number depending on the light curtain
for which the configuration is to be made.
If the wrong light curtain was selected, you cannot load the configuration.
Step 2: Transfer configuration to a light curtain
Connect the adapter to the light curtain (see section "Connection").
Press the button
until the symbol
is shown on the display.
Once the upload has been completed successful, a corresponding
configuration report is saved in the adapter. A maximum of 10 read
processes can be performed in succession. Then load the configuration
reports via PSENopt Configurator to perform further read processes.
When the load procedure is complete the configuration remains saved in the
adapter: It can then be read to other light curtains (a new report is created for each
upload).
Step 3: Downloading the reports and checking the safety
light curtain configuration
Connect the adapter to the Ethernet network and the supply (see section
"Stand-alone connection").
Then load all the reports saved in the adapter via PSENopt Configurator.
Each configuration report states the serial number of the safety light curtain, in
which the corresponding configuration was read, and all the configuration
parameters.
Before starting normal plant operation it must be checked
that the configured light curtains work to the purpose for
which they are intended.
ERROR LOG
When PSEN op Advanced Programming Adapter is permanently connected to a
light curtain, an error log is written on the adapter. This can be made via the
Software PSENopt Configurator. Detailed diagnostics of random states is
therefore possible.
It is only possible to record errors via the adapter when the Type4 light curtain was
configured with the software.
An error is written to the log when this error can be recovered via RESET.
The maximum number of logs in the adapter depends on the type of cascading: 7
logs per cascading with 3 light curtains, 11 logs per cascading with 2 light curtains,
23 logs per cascading with 1 light curtain.
When the adapter is offset from one light curtain to the next, or the configuration of
the light curtain changes, the current log is deleted and a new log is created.
Connect the adapter to the Ethernet network and the supply (see section
"Stand-alone connection").
In PSENopt Configurator select "Open log of the safety light curtain" to load and
display the logs saved in the adapter.
The log of the safety system includes:
• A report on the safety system with detailed configuration of the light curtain that
the log refers to.
• One or several logs with detailed information on the errors.
SPECIFIC STATUS DISPLAY
When the adapter is connected to a safety light curtain, detailed information on the
status of the light curtain is shown in the
7 segment display.
Further information on the messages on the user interface see: Chapter
"Diagnostics" in the PSEN op light curtain operating manual.
ERROR MESSAGES
OSSD error
Microcontroller error
Optical system error
EDM error
Restart error
Communication error
BCM Configuration error
ACM configuration error
Muting lamp error
STATUS MESSAGES
Light curtain in ALIGN mode, aligned correctly
Light curtain in ALIGN mode, not aligned
Light curtain in ALIGN mode, last optics not aligned
Light curtain in ALIGN mode, optics not aligned
Light curtain in ALIGN mode, middle beam not aligned
Safety light curtain in interlock, activate RESTART
Advanced configuration via PSENopt Configurator is
running
Muting function active
Safety light curtain process ready for override
Override function active
Wrong wiring on the override
Blanking zones limits not observed.
Blanking function active