Dvrt41 direct vent gas fireplace, Mantels, Clearance to combustibles – Vermont Casting DVRT41 User Manual

Page 6: Hearth, Mantel chart

background image

6

DVRT41 Direct Vent Gas Fireplace

10006740

Mantels

The height that a combustible mantel is fitted above
the fireplace is dependent on the depth of the mantel.
This also applies to the distance between the mantel
leg (if fitted) and the fireplace.

For the correct mounting height and widths, refer to
Figures 4a, 4b and the Mantel Chart below.

The distances and reference points are not affected by
the fitting of a bay window front trim kit.

Noncombustible mantels and legs may be installed at
any height and width around the appliance. When
using paint or lacquer, it must be heat resistant to
prevent discoloration.

Clearance to Combustibles

Top of unit to ceiling ................................. 36” (914mm)
Front of unit to combustibles ................... 36” (914mm)
Appliance

Top of standoff ........................................ 0” (0mm)
Bottom ..................................................... 0” (0mm)
Side ......................................................... 0” (0mm)
Back ......................................................... 0” (0mm)

Venting
Concentric sections of DV Vent ................... 1” (25mm)
Nonconcentric sections of DV Vent

Sides and bottom .................................. 1” (25mm)
Top ........................................................ 2” (51mm)

J

F

G

H

I

Mantel
Leg

Black
Surround
Face

CFM164a

O

N

M

L

K

Side of
Combustion Chamber

CFM170

Fig. 4b Combustible mantel leg minimum installation.

Mantel

Mantel Leg from Side

Ref.

Leg Depth

Ref.

of Comb. Opening

F

10” (254mm)

K

11

¹⁄₂

” (292mm)

G

8” (203mm)

L

9

¹⁄₂

” (241mm)

H

6” (152mm)

M

7

¹⁄₂

” (191mm)

I

4” (101mm)

N

5

¹⁄₂

” (140mm)

J

2” (51mm)

O

3

¹⁄₂

’” (89mm)

Hearth

A hearth is not mandatory, but is recommended for
aesthetic purposes. We recommend a noncombustible
hearth which projects out 12” (305mm) or more from
the front of the fireplace.

Cold climate installation recommendation:

When installing this unit against a non-
insulated exterior wall or chase, it is
mandatory that the outer walls be insu-
lated to conform to applicable insulation
codes.

A

B

C

D

E

V

W

X

Y

Z

Fireplace

Louvre
Assembly Top

Top of Combustion
Chamber

Bottom of Door Trim

CFM146

Fig. 4a Combustible mantel minimum installation.

Mantel Chart

Mantel Shelf

Mantel from Top

Ref.

or Breast Plate

Ref. of Comb. Chamber

Depth

V

10” (254mm)

A

19” (483mm)

W

8” (203mm)

B

17” (432mm)

X

6” (152mm)

C

15” (381mm)

Y

4” (101mm)

D

13” (330mm)

Z

2” (51mm)

E

11” (279mm)

Maintain minimum 3/4”
(19mm) clearance to
combustible