DVRT41 Direct Vent Gas Fireplace

10006740

LED Count

Service Action

8

Replace valve

7

Confirm stepper motor connection
exists

5

Confirm fan connection exists and
works

4

Confirm gas type; jumper in place

3

Replace thermopiles

2

Turn fan ON

NOTE: Some keys are not active.

2. Slide the Remote/Local switch to REMOTE and

teach the valve a transmitter (refer to Item 6, page
1). The Error Code will clear itself after approxi-
mately 1

¹⁄₂

minutes and return to normal operation.

If the setting is above

room temperature on

the transmitter, does the

main valve and fan turn

on?

If the setting is below
room temperature on

the transmitter, does

the main valve and fan

turn off?

Turn pilotstat knob to

OFF to turn valve

completely off

Auto Path

Yes

Yes

No

If the manual switch is

set to REMOTE, press

the mode button to

display AUTO on the

transmitter. Does the

transmitter display the

room and temperature

setting?

Move switch from

LOCAL to RE-

MOTE. Press any

key within 30

seconds.

No