Initial Start-Up:

When power is applied to the unit, the control will briefly

display all symbols, and the Compressor symbol will be

displayed (if unit is calling for cooling). There may be a brief

delay prior to the evaporator fans turning on.

Set Point:

The set point is set from the factory (WhisperKool) at 55°.

It can be adjusted by the customer between 50° and 70° in

one degree increments.

Cooling Operation:

Cooling is activated once the bottle probe senses a

temperature that is 1° greater than the set point. The

controller then energizes the solenoid relay which activates

the solenoid. The evaporator fans operate with the

compressor. The unit provides cooling until the bottle probe

senses the set point. At this point the solenoid relay is de-

energized which stops the flow of refrigerant through the

evaporator coil. The compressor will continue to run until

the low side pressure reaches 5 psi. The evaporator fans will

continue to run for 1 minute to re-evaporate any moisture

from the evaporator coil.

Humidity Features:

The FDC parameter can be increased to allow the evaporator

fans to run for a longer period of time after the compressor

turns off, allowing more moisture to be re-evaporated into

the cellar.

Defrost/Anti-frost:

When the evaporator probe senses a temperature of

26 degrees for 5 minutes, the unit will go into Anti-frost

mode. This will shut down the compressor and allow the

evaporator fans to run to evaporate any frost accumulation

on the coil. The compressor will remain off until the

evaporator coil reaches 40°, or for a maximum of 10 minutes.

The unit will then return to normal operation.

If the evaporator is not above 26 degrees after the anti-

frost sequence has ended, the red error light will display in

the upper right corner. Alarm “Ad3” will be recorded in the

alarm folder, meaning that the anti-frost sequence ended

based on time. The unit will run for 5 minutes and then enter

another Anti-Frost cycle. This sequence will continue until

the evaporator temperature increases above 26°.

“Def” will be displayed during anti-frost. If the anti-frost

sequence is less than 5 minutes, the control will not allow

the compressor to start until 5 minutes has elapsed. This is

to prevent short cycling of the compressor.

Holding down the up button for approximately five seconds

manually starts the Anti-frost sequence, but only if the

evaporator is below 40 degrees (defrost end temperature).

If the evaporator is above 40 degrees, the display will blink

three times and continue normal operation.

Display:

The bottle probe temperature is displayed by default.

“Def” is displayed during anti-frost. The bottle probe and

evaporator probe temperatures can all be accessed by

pushing the set button and scrolling through PB1 (bottle

probe) and PB2 (evaporator probe).

Safety Features:

Once the solenoid relay is de-energized the controller must

wait 5 minutes before re-energizing the relay. This prevents

the compressor from repeatedly turning off and on. If the

unit is calling for cooling during this time, the compressor

symbol will blink indicating that cooling is needed but the

control is waiting for the anti-short cycle delay.

In the event of a faulty bottle probe, the compressor will

cycle off for 10 minutes and on for 40 minutes. E1 will will be

displayed on the screen.

Alarms:

If the bottle temperature reaches 8 degrees above the set

point, a red light will blink in the upper right corner of the

display. The set button can then be pressed to reach the

alarm menu. The menu will display “AH1” indicating a high

bottle temperature. The same thing will happen if the bottle

temperature reaches 8 degrees below the set point, except

the alarm will read “AL1”. These alarms will not display for the

first 10 hours after the unit is turned on to allow the cellar

to reach temperature. They will also wait one hour after an

anti-frost cycle before displaying.

In the event of a faulty evaporator probe E2 will flash on the

screen intermittently. The red alarm light will be displayed in

the upper right corner. The unit will go through one anti-

frost sequence every 24 hours.

Press the set button and enter the Al folder to view any

current alarms that are not flashing on the display.

UNIT OPERATION